| 2021-08-25 13:43:06 | PLAN REVIEW / NFIP |
| | |
| | CHRISTOPHER S. THROOP, C.B.O., CFM |
| | PLANS EXAMINER II PX3169/SFP306 |
| | INSPECTOR BN4338 |
| | BUILDING OFFICIAL BU1635 |
| | ASFPM CERTIFIED FLOODPLAIN MANAGER US-21-11935 |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | CITY OF WEST PALM BEACH |
| | (561) 805-6726 |
| | [email protected] |
| | |
| | |
| | CODES IN EFFECT: |
| | 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST |
| | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| | CHAPTER 1 ADMINISTRATION |
| | CITY ORDINANCE NO. 4658-16 |
| | |
| | |
| | NOTICE: |
| | |
| | THE 2-STORY SFR ENCROACHES INTO A SPECIAL FLOOD HAZARD |
| | AREA (SFHA). FLOOD ZONE AE WITH A BASE FLOOD ELEVATION |
| | (BFE) OF 6.0 FEET NAVD. THE DESIGN FLOOD ELEVATION |
| | (DFE) SHALL BE NOT LESS THAN 8.0 FEET NAVD. |
| | |
| | |
| | 3 ELEVATION CERTIFICATES (EC) ARE REQUIRED FOR THE |
| | 2-STORY SFR |
| | |
| | A CONSTRUCTION DRAWING ELEVATION CERTIFICATE IS |
| | REQUIRED AT TIME OF PERMIT APPLICATION. |
| | |
| | A BUILDING UNDER CONSTRUCTION ELEVATION CERTIFICATE IS |
| | REQUIRED AT PLACEMENT OF 1ST FLOOR. |
| | |
| | A FINISHED CONSTRUCTION ELEVATION CERTIFICATE IS |
| | REQUIRED AND SHALL BE SUBMITTED FOR REVIEW AND APPROVAL |
| | PRIOR TO THE ISSUANCE OF THE CERTIFICATE OF OCCUPANCY. |
| | NOTE: YOU MAY SUBMIT THIS EC FOR REVIEW AFTER FINAL |
| | GRADE AND PLACEMENT OF EQUIPMENT SERVICING THE |
| | BUILDING. |
| | |
| | 1ST REVIEW OF CONSTRUCTION DRAWING ELEVATION |
| | CERTIFICATE. |
| | |
| | RESULTS: DENIED |
| | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| | |
| | 1. FEMA FORM 086-0-33 (7/15) IS OUT OF DATE. SUBMIT |
| | ELEVATION CERTIFICATES ON FEMA FORM 086-0-33 (12/19) |
| | WITH AN EXPIRATION DATE OF NOVEMBER 30, 2022. |
| | |
| | 2. ELEVATIONS ON PLANS ARE IN NGVD. ELEVATIONS ON EC |
| | ARE IN NAVD PER SECTION C2 IF THIS IS CORRECT, PROVIDE |
| | A CONVERSION FACTOR IN SECTION D - COMMENTS. |
| | |
| | 3. SECTION B8 SHOULD ONLY CONTAIN FLOOD ZONES WITH BASE |
| | FLOOD ELEVATION DATUM. X-500 IS NOT A SPECIAL FLOOD |
| | HAZARD AREA AND HAS NO BASE FLOOD ELEVATION |
| | REQUIREMENTS. ENTER ONLY AE IN SECTION B8. |
| | |
| | 4. INCLUDE THE ELEVATION OF THE PROPOSED GENERATOR IN |
| | SECTION D - COMMENTS. (SEE SITE PLAN) |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |