2021-06-22 10:27:1721060386 777 S FLAGLER DR # 1400 W
  
 PLUMBING APPROVED
  
 PROVISO: PLAN SHEETS P0.1, P2.1, P3.1 AND P4.1 SHALL BE
 REVISED TO REFLECT THE RED-LINED COMMENTS ON THOSE
 PAGES AND ARE NOTED IN THIS PROVISO. THE REVISED PLANS
 SHALL BE SUBMITTED, APPROVED AND ON SITE PRIOR TO THE
 FIRST INSPECTION.
 ...PER WPB FBC 107.2.1, PROVIDE MATERIAL SPECIFICATION
 FOR SANITARY DRAIN PUMP DISCHARGE PIPING
 ...PROVIDE FULL OPEN VALVE ON SANITARY DRAIN PUMP
 DISCHARGE PER FBC PL 712.2
 ...PROVIDE ACCESSIBLE FULL OPEN VALVES AT TOP OF WATER
 DOWNFEED PIPES PER FBC PL 605.1(5)
  
  
 ALL WORK PER STATE AND CITY CODES SUBJECT TO FIELD
 INSPECTOR'S APPROVAL
  