| Date |
Text |
| 2021-06-10 13:47:23 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1 |
| | WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL |
| | MANUAL REVISED 2017 |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 |
| | 7TH EDITION |
| | FBC ACC = FLORIDA ACCESSIBILITY CODE 2020 7TH EDITION |
| | FBC EX = FLORIDA EXISTING BUILDING CODE 2020 7TH |
| | EDITION |
| | FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION |
| | FAC= FLORIDA ADMINISTRATIVE CODE |
| | FS = FLORIDA STATUTES |
| | |
| | |
| | 1ST REVIEW |
| | 'PROVISO: MANUFACTURER SPECIFICATION/INSTALLATION |
| | MANUAL FOR EWH-1 TANKLESS WATER HEATER AND THE DRAIN |
| | PUMP SHALL BE SUBMITTED WITH ENGINEER'S APPROVAL TO THE |
| | BUILDING DEPARTMENT FOR REVIEW AND APPROVAL AND SHALL |
| | BE ON SITE PRIOR TO FINAL INSPECTION. SEE WPB FBC |
| | 107.3.4.1 DEFERRED SUBMITTALS; FOR THE PURPOSES OF THIS |
| | SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE |
| | PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE |
| | TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO |
| | THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD. |
| | DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR |
| | APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED |
| | DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST |
| | THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS |
| | FOR REVIEW BY THE BUILDING OFFICIAL. DOCUMENTS FOR |
| | DEFERRED SUBMITTAL ITEMS SHALL BE SUBMITTED TO THE |
| | REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE |
| | WHO SHALL REVIEW THEM AND FORWARD THEM TO THE BUILDING |
| | OFFICIAL WITH A NOTATION INDICATING THAT THE DEFERRED |
| | SUBMITTAL DOCUMENTS HAVE BEEN REVIEWED AND FOUND TO BE |
| | IN GENERAL CONFORMANCE TO THE DESIGN OF THE BUILDING. |
| | THEY SHALL BE SUBMITTED TO, APPROVED BY THE BUILDING |
| | OFFICIAL AND ON SITE PRIOR TO FINAL INSPECTION. PROCEED |
| | AT YOUR OWN RISK. |
| | THIS MAY BE DONE BY NOTING SUCH IN THE RESPONSE LETTER |
| | TO THIS REVIEW. |
| | |
| | |
| | PLUMBING COMMENTS: DENIED |
| | |
| | A REVIEW OF MINIMUM PLUMBING FIXTURE REQUIREMENTS AS |
| | REQUIRED BY FBC ACC IS PART OF THE PLUMBING REVIEW |
| | PROCESS BUT IS TYPICALLY ADDRESSED ON THE ARCHITECTURAL |
| | PLANS. ANY COMMENTS CONCERNING THESE REQUIREMENTS MUST |
| | BE SATISFACTORILY ADDRESSED PRIOR TO A PLUMBING REVIEW |
| | APPROVAL. |
| | |
| | 1.COFFEE RM 1404: PER WPB FBC 107.2.1, PROVIDE |
| | ELEVATION DETAIL SHOWING HOW CLEAR FLOOR SPACE FORWARD |
| | APPROACH (SHOWN ON A1.2 LIFE SAFETY) TO SINK WILL BE |
| | ACCOMPLISHED SHOWING COMPLIANCE WITH FBC ACC 306 KNEE |
| | AND TOE CLEARANCE AS REQUIRED BY FBC ACC 602.2 WILL BE |
| | ACCOMPLISHED. |
| | PLEASE NOTE, PER FBC ACC 606.5 EXPOSED PIPES AND |
| | SURFACES. WATER SUPPLY & DRAINPIPES UNDER LAVATORIES |
| | AND SINKS SHALL BE INSULATED OR OTHERWISE CONFIGURED TO |
| | PROTECT AGAINST CONTACT. |
| | |
| | 2.PER WPB FBC 107.2.1, IDENTIFY AND SHOW LOCATION OF |
| | SERVICE SINK AND IDENTIFY THE DRINKING FOUNTAIN ON THE |
| | 14TH FLOOR. FBC PL 403.1. |
| | |
| | 3.SANITARY AS SHOWN IN RISER DIAGRAM FROM PUMPS TO |
| | CONNECTION WITH STACK IS A PUMP DISCHARGE. MATERIAL |
| | (PIPE, VALVES AND FITTINGS) SHALL BE PRESSURE RATED PER |
| | FBC PL 712.3.3, 712.3.3.1 AND 712.3.3.2. PROVIDE |
| | MATERIAL SPECIFICATION FOR PUMP DISCHARGE PIPING. |
| | CONNECTION TO SANITARY STACK SHALL BE MADE WITH AN |
| | UPRIGHT WYE. |
| | IF THE INTENT IS FOR THE HORIZONTAL 2 INCH AND 3 INCH |
| | PIPING TO DRAIN BY GRAVITY CONSTRUCTED OF PIPE AND |
| | FITTINGS COMPLYING WITH FBC PL CHAPTER 7, THEN PROVIDE |
| | A VENT FOR THE GRAVITY DRAINAGE SYSTEM A MINIMUM 10 |
| | PIPE DIAMETERS DOWNSTREAM OF PUMP DISCHARGE CONNECTION. |
| | VENT SHALL CONNECT TO THE HORIZONTAL SANITARY AT THE |
| | TOP WITH VERTICAL RISE BEFORE CONNECTING TO BRANCH |
| | VENT. PUMP DISCHARGE TO DROP VERTICALLY INTO HORIZONTAL |
| | AND SHALL BE PRESSURE RATED TO THE POINT THAT IT |
| | CONNECTS TO THE SANITARY DRAINAGE FITTING IN THE |
| | HORIZONTAL DRAIN. NOTATE ON THE PLANS THE ACTUAL |
| | POINT(S) OF CONNECTION PUMP DISCHARGE TO SANITARY |
| | GRAVITY DRAINAGE. PROVIDE NOTE "PER FBC PL 704.1, |
| | HORIZONTAL DRAINAGE PIPING SHALL BE INSTALLED IN |
| | UNIFORM ALIGNMENT AT UNIFORM SLOPES; TABLE 704.1, 2 |
| | INCH PIPE SHALL BE INSTALLED WITH MINIMUM 2% SLOPE AND |
| | 3 INCH PIPE SHALL BE INSTALLED WITH MINIMUM 1% SLOPE" |
| | |
| | 4.PER WPB FBC 107.2.1, PROVIDE SCHEDULE FOR SANITARY |
| | DRAIN PUMP; MANUFACTURER, MODEL #, GPM, TDH AND |
| | ELECTRICAL CHARACTERISTICS. |
| | |
| | 5.PER WPB FBC 107.2.1, PROVIDE A SCHEMATIC DETAIL OF |
| | THE SANITARY DRAIN PUMP AND FIXTURE BEING SERVED. SHOW |
| | TRAPPED FIXTURE DRAIN, VENTING, DISCHARGE RISER AND |
| | REQUIRED VALVES. COMPLY WITH FBC PL 712 AND APPLICABLE |
| | SECTIONS OF FBC PL CHAPTER 9. PLEASE NOTE, PER FBC PL |
| | 301.7, IN INSTANCES WHERE CONFLICTS OCCUR BETWEEN THIS |
| | CODE AND THE MANUFACTURER'S INSTALLATION INSTRUCTIONS, |
| | THE MORE RESTRICTIVE PROVISIONS SHALL APPLY. |
| | |
| | 6.AC CONDENSATE- PER WPB CODE OF ORDINANCE CHAPTER 90, |
| | ARTICLE 3, SECTION 90-12B5, A/C CONDENSATE (INTERPRET |
| | THIS AS ANY CONDENSATION FROM EVAPORATOR COILS) SHALL |
| | NOT DISCHARGE TO THE CITY UTILITIES SANITARY SEWAGE |
| | INFRASTRUCTURE WITHOUT PERMISSION FROM THE UTILITIES |
| | DEPARTMENT. YOU MAY CONTACT MR. MANNY GONZALES IN |
| | ENGINEERING AT 561-494-1128 FOR ADDITIONAL INFORMATION. |
| | MOVING FORWARD, DISCHARGE THE CONDENSATE TO THE STORM |
| | SYSTEM WITH A BACKWATER VALVE (PROVIDE DETAIL), |
| | EXISTING CONDENSATE SYSTEM OR AN EXTERIOR DRYWELL |
| | (PROVIDE DRYWELL DETAIL AND ROUTING). |
| | |
| | 7. PER WPB FBC 107.2.1, IDENTIFY THE COFFEEMAKER COLD |
| | WATER OUTLET ON WATER RISER AND PLAN VIEW DISTRIBUTION. |
| | |
| | 8. PER WPB FBC 107.2.1, SIZE ALL NEW WATER DISTRIBUTION |
| | ON WATER RISER. |
| | |
| | 9.PER FBC PL 606.1(5), PROVIDE ACCESSIBLE FULL OPEN |
| | VALVES AT THE TOP OF THE WATER DOWN FEED PIPES. |
| | |
| | 10.PER FBC PL 606.1(2), PROVIDE ACCESSIBLE FULL OPEN |
| | VALVE UPSTREAM OF COMMON/TENANT WALL PENETRATION TO BE |
| | ACCESSIBLE TO BUILDING MAINTENANCE AT ANYTIME. |
| | |
| | 11.PER FBC PL 503.1 AND 606.1(8), PROVIDE ACCESSIBLE |
| | FULL OPEN VALVE IN COLD WATER BRANCH TO THE TANKLESS |
| | WATER HEATER(S) |
| | |
| | END OF COMMENTS. |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED |
| | AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS. |
| | |
| | JERALD SMITH |
| | PLUMBING PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | EMAIL [email protected] |
| | MOBILE 561-246-0882 |
| | PLEASE NOTE THAT I TYPICALLY WORK ON TUESDAYS AND |
| | THURSDAYS |
| | |
| | 21060386 777 S FLAGLER DR # 1400 W |