Plan Review Notes
Plan Review Notes For Permit 21060386
Permit Number 21060386
Review Stop P
Sequence Number 1
Notes
Date Text
2021-06-10 13:47:23CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2020 7TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2020 7TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
  
 1ST REVIEW
 'PROVISO: MANUFACTURER SPECIFICATION/INSTALLATION
 MANUAL FOR EWH-1 TANKLESS WATER HEATER AND THE DRAIN
 PUMP SHALL BE SUBMITTED WITH ENGINEER'S APPROVAL TO THE
 BUILDING DEPARTMENT FOR REVIEW AND APPROVAL AND SHALL
 BE ON SITE PRIOR TO FINAL INSPECTION. SEE WPB FBC
 107.3.4.1 DEFERRED SUBMITTALS; FOR THE PURPOSES OF THIS
 SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE
 PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE
 TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO
 THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD.
 DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR
 APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST
 THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS
 FOR REVIEW BY THE BUILDING OFFICIAL. DOCUMENTS FOR
 DEFERRED SUBMITTAL ITEMS SHALL BE SUBMITTED TO THE
 REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE
 WHO SHALL REVIEW THEM AND FORWARD THEM TO THE BUILDING
 OFFICIAL WITH A NOTATION INDICATING THAT THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN REVIEWED AND FOUND TO BE
 IN GENERAL CONFORMANCE TO THE DESIGN OF THE BUILDING.
 THEY SHALL BE SUBMITTED TO, APPROVED BY THE BUILDING
 OFFICIAL AND ON SITE PRIOR TO FINAL INSPECTION. PROCEED
 AT YOUR OWN RISK.
 THIS MAY BE DONE BY NOTING SUCH IN THE RESPONSE LETTER
 TO THIS REVIEW.
  
  
 PLUMBING COMMENTS: DENIED
  
 A REVIEW OF MINIMUM PLUMBING FIXTURE REQUIREMENTS AS
 REQUIRED BY FBC ACC IS PART OF THE PLUMBING REVIEW
 PROCESS BUT IS TYPICALLY ADDRESSED ON THE ARCHITECTURAL
 PLANS. ANY COMMENTS CONCERNING THESE REQUIREMENTS MUST
 BE SATISFACTORILY ADDRESSED PRIOR TO A PLUMBING REVIEW
 APPROVAL.
  
 1.COFFEE RM 1404: PER WPB FBC 107.2.1, PROVIDE
 ELEVATION DETAIL SHOWING HOW CLEAR FLOOR SPACE FORWARD
 APPROACH (SHOWN ON A1.2 LIFE SAFETY) TO SINK WILL BE
 ACCOMPLISHED SHOWING COMPLIANCE WITH FBC ACC 306 KNEE
 AND TOE CLEARANCE AS REQUIRED BY FBC ACC 602.2 WILL BE
 ACCOMPLISHED.
 PLEASE NOTE, PER FBC ACC 606.5 EXPOSED PIPES AND
 SURFACES. WATER SUPPLY & DRAINPIPES UNDER LAVATORIES
 AND SINKS SHALL BE INSULATED OR OTHERWISE CONFIGURED TO
 PROTECT AGAINST CONTACT.
  
 2.PER WPB FBC 107.2.1, IDENTIFY AND SHOW LOCATION OF
 SERVICE SINK AND IDENTIFY THE DRINKING FOUNTAIN ON THE
 14TH FLOOR. FBC PL 403.1.
  
 3.SANITARY AS SHOWN IN RISER DIAGRAM FROM PUMPS TO
 CONNECTION WITH STACK IS A PUMP DISCHARGE. MATERIAL
 (PIPE, VALVES AND FITTINGS) SHALL BE PRESSURE RATED PER
 FBC PL 712.3.3, 712.3.3.1 AND 712.3.3.2. PROVIDE
 MATERIAL SPECIFICATION FOR PUMP DISCHARGE PIPING.
 CONNECTION TO SANITARY STACK SHALL BE MADE WITH AN
 UPRIGHT WYE.
 IF THE INTENT IS FOR THE HORIZONTAL 2 INCH AND 3 INCH
 PIPING TO DRAIN BY GRAVITY CONSTRUCTED OF PIPE AND
 FITTINGS COMPLYING WITH FBC PL CHAPTER 7, THEN PROVIDE
 A VENT FOR THE GRAVITY DRAINAGE SYSTEM A MINIMUM 10
 PIPE DIAMETERS DOWNSTREAM OF PUMP DISCHARGE CONNECTION.
 VENT SHALL CONNECT TO THE HORIZONTAL SANITARY AT THE
 TOP WITH VERTICAL RISE BEFORE CONNECTING TO BRANCH
 VENT. PUMP DISCHARGE TO DROP VERTICALLY INTO HORIZONTAL
 AND SHALL BE PRESSURE RATED TO THE POINT THAT IT
 CONNECTS TO THE SANITARY DRAINAGE FITTING IN THE
 HORIZONTAL DRAIN. NOTATE ON THE PLANS THE ACTUAL
 POINT(S) OF CONNECTION PUMP DISCHARGE TO SANITARY
 GRAVITY DRAINAGE. PROVIDE NOTE "PER FBC PL 704.1,
 HORIZONTAL DRAINAGE PIPING SHALL BE INSTALLED IN
 UNIFORM ALIGNMENT AT UNIFORM SLOPES; TABLE 704.1, 2
 INCH PIPE SHALL BE INSTALLED WITH MINIMUM 2% SLOPE AND
 3 INCH PIPE SHALL BE INSTALLED WITH MINIMUM 1% SLOPE"
  
 4.PER WPB FBC 107.2.1, PROVIDE SCHEDULE FOR SANITARY
 DRAIN PUMP; MANUFACTURER, MODEL #, GPM, TDH AND
 ELECTRICAL CHARACTERISTICS.
  
 5.PER WPB FBC 107.2.1, PROVIDE A SCHEMATIC DETAIL OF
 THE SANITARY DRAIN PUMP AND FIXTURE BEING SERVED. SHOW
 TRAPPED FIXTURE DRAIN, VENTING, DISCHARGE RISER AND
 REQUIRED VALVES. COMPLY WITH FBC PL 712 AND APPLICABLE
 SECTIONS OF FBC PL CHAPTER 9. PLEASE NOTE, PER FBC PL
 301.7, IN INSTANCES WHERE CONFLICTS OCCUR BETWEEN THIS
 CODE AND THE MANUFACTURER'S INSTALLATION INSTRUCTIONS,
 THE MORE RESTRICTIVE PROVISIONS SHALL APPLY.
  
 6.AC CONDENSATE- PER WPB CODE OF ORDINANCE CHAPTER 90,
 ARTICLE 3, SECTION 90-12B5, A/C CONDENSATE (INTERPRET
 THIS AS ANY CONDENSATION FROM EVAPORATOR COILS) SHALL
 NOT DISCHARGE TO THE CITY UTILITIES SANITARY SEWAGE
 INFRASTRUCTURE WITHOUT PERMISSION FROM THE UTILITIES
 DEPARTMENT. YOU MAY CONTACT MR. MANNY GONZALES IN
 ENGINEERING AT 561-494-1128 FOR ADDITIONAL INFORMATION.
 MOVING FORWARD, DISCHARGE THE CONDENSATE TO THE STORM
 SYSTEM WITH A BACKWATER VALVE (PROVIDE DETAIL),
 EXISTING CONDENSATE SYSTEM OR AN EXTERIOR DRYWELL
 (PROVIDE DRYWELL DETAIL AND ROUTING).
  
 7. PER WPB FBC 107.2.1, IDENTIFY THE COFFEEMAKER COLD
 WATER OUTLET ON WATER RISER AND PLAN VIEW DISTRIBUTION.
  
 8. PER WPB FBC 107.2.1, SIZE ALL NEW WATER DISTRIBUTION
 ON WATER RISER.
  
 9.PER FBC PL 606.1(5), PROVIDE ACCESSIBLE FULL OPEN
 VALVES AT THE TOP OF THE WATER DOWN FEED PIPES.
  
 10.PER FBC PL 606.1(2), PROVIDE ACCESSIBLE FULL OPEN
 VALVE UPSTREAM OF COMMON/TENANT WALL PENETRATION TO BE
 ACCESSIBLE TO BUILDING MAINTENANCE AT ANYTIME.
  
 11.PER FBC PL 503.1 AND 606.1(8), PROVIDE ACCESSIBLE
 FULL OPEN VALVE IN COLD WATER BRANCH TO THE TANKLESS
 WATER HEATER(S)
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 MOBILE 561-246-0882