2021-07-06 10:11:3104/07/21 1ST GAS REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. ON SHEET E0.0 FOR THE CODE REFERENCE IT SATES 2017
 FBC; PLEASE PROVIDE THE CORRECT AND CURRENT GAS CODE
 CYCLE PER THE WPB AMENDMENTS TO THE FBC SEC. 102.3
 APPLICATION OF REFERENCES.
  
 2. GAS RISER DIAGRAM REQUIRED PER THE WPB AMENDMENTS TO
 THE FBC SEC. 107.3.5.1.5 (9) COMMERCIAL GAS.
  
 A. SHOW THE TYPE OF PIPE MATERIAL BEING INSTALLED, ALL
 PIPE SIZES, AND THE CORRESPONDING EHD NUMBER OF THE
 CORRUGATED STAINLESS-STEEL TUBING (IF APPLICABLE) FOR
 EACH PIPE AND CLEARLY SHOWS THE LENGTH OF ALL CUT
 SECTIONS OF PIPE PER 2020 FBC FG SECS. 402.4.1,
 402.4.2.
  
 B. TYPE OF GAS (LP OR NATURAL) PER THE WPB AMENDMENTS
 TO THE FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS.
  
 C. PLEASE LABEL AND SHOW ALL SHUT-OFF, DRIP LEG, AND
 UNIONS IN FRONT OF REGULATOR 1? OF EITHER SIDE PER THE
 2020 FBC RES. SEC G2421.2.
  
 D. INDICATE THE DELIVERY PRESSURE (PSI) OF THE SYSTEM
 ON THE PLAN PER THE 2020 FBC FG SEC. 402.2.
  
 E. PLEASE SHOW ALL UNIONS IN FRONT OF REGULATOR 1' OF
 EITHER SIDE PER THE 2020 FBC FG SEC 410.2.
  
 F. PLEASE LABEL THE SHUTOFF VALVE ON GAS ISOMERIC PER
 THE 2020 FBC FG SEC. 409.5.
  
 3. A SUB GAS PERMIT IS REQUIRED BY A LICENSED
 CONTRACTOR FOR THE SCOPE OF WORK PER THE WPB AMENDMENTS
 TO THE FBC SEC. 105.1.
  
 4. SUBMIT SIZING TABLE USED IN THE DESIGN FOR THE GAS
 SYSTEM OR PLACE A NOTE ON BOTH SETS OF PLANS LISTING
 THE SIZING TABLES FROM GAS CODES OR ANOTHER STANDARD
 THAT WERE USED IN THE DESIGN OF THIS SYSTEM PER THE
 2017 FBC FG SEC. 402.3 OR 2017 FBC RES. SEC. G2413.3.
  
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION,
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  