| Plan Review Notes For Permit 21060354 |
| Permit Number |
21060354 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2021-06-18 15:08:40 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | FLORIDA BUILDING CODE 2020 7TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED | | | NFPA 70 2017 EDITION | | | | | | JAKE LEAHY BN, BU, PX | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | 1) PLEASE SUBMIT A SIGNED CONTRACT FOR THE WORK | | | INCLUDING THE CONCRETE PAD. THIS PROJECT INCLUDES | | | REFEEDING A NEW TRSNSFER SWITCH WHICH SHALL ALSO BE | | | INCLUDED IN THE VALUE. | | | | | | 2) FAULT CURRENT CALCULATION REQUIRED 110.9, 110.10 | | | | | | 3) COMPLIANCE WITH 240.87 REQUIRED, PLEASE INDICATE | | | METHOD TO BE USED ON PLAN. 240.87 | | | | | | 4) LOAD CALCULATION FOR NEW GENERATOR TO SUPPLY WHOLE | | | BUILDING REQUIRED 220, 215.5 |
|