2021-06-18 15:08:40ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 1) PLEASE SUBMIT A SIGNED CONTRACT FOR THE WORK
 INCLUDING THE CONCRETE PAD. THIS PROJECT INCLUDES
 REFEEDING A NEW TRSNSFER SWITCH WHICH SHALL ALSO BE
 INCLUDED IN THE VALUE.
  
 2) FAULT CURRENT CALCULATION REQUIRED 110.9, 110.10
  
 3) COMPLIANCE WITH 240.87 REQUIRED, PLEASE INDICATE
 METHOD TO BE USED ON PLAN. 240.87
  
 4) LOAD CALCULATION FOR NEW GENERATOR TO SUPPLY WHOLE
 BUILDING REQUIRED 220, 215.5