Plan Review Notes For Permit 21060283
Permit Number 21060283
Review Stop Z
Sequence Number 1
Notes
Date Text
2021-07-02 11:26:20** FAILED **
  
 PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE
 COMMENTS IN WRITING AND/OR ON THE PLANS WHERE
 APPLICABLE:
  
 1.) SURVEY IS OUTDATED AND DOES NOT APPEAR TO REFLECT
 THE CURRENT CONDITIONS ON THE PROPERTY. IT IS ALSO VERY
 DIFFICULT TO SEE THE PROPERTY LINES FOR THE PROPERTY.
 PLEASE PROVIDE AN UPDATED SIGNED AND SEALED SURVEY.
  
 2.) AWNING CANNOT ENCROACH MORE THAN 4 FT. INTO A
 REQUIRED SETBACK. PLEASE PROVIDE SETBACK DIMENSIONS OF
 THE PROPOSED AWNING TO THE PROPERTY LINE. [ZLDR
 S.94-305(B)(5)]
  
 3.) IT IS NOT CLEAR IF THE PROPOSED AWNING WILL
 ENCROACH/ELIMINATE PARKING ON THE SOUTH SIDE OF THE
 BUILDING. PLEASE CLARIFY. IF PARKING ALONG THE SOUTH
 SIDE OF THE BUILDING IS TO BE REMOVED, THEN ADDITIONAL
 INFORMATION WILL BE REQUIRED ON THE EXISTING USE AND
 EXISTING NUMBER OF PARKING SPACES PROVIDED ON SITE. IF
 THE SITE IS DEFICIENT IN THE NUMBER OF REQUIRED PARKING
 SPACES, THEN THE EXISTING PARKING CANNOT BE REMOVED ON
 THE PROPERTY.
  
 4.) MINOR DISCREPANCY WITH THE DIMENSIONS OF THE
 AWNING. DETAILS SHEET STATES A 15 FT. X 60 FT. AWNING
 AND SURVEY SHOWS A 15 FT. BY 59 FT. AWNING. PLEASE
 ADDRESS FOR CONSISTENCY.
  
 5.) INFORMATION SHALL BE PROVIDED ON THE VERTICAL
 CLEARANCE OF THE AWNING FROM GRADE.
  
 NOTES:
  
 * ANY REVISIONS MAY RESULT IN ADDITIONAL COMMENTS.
  
 * CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE ARE
 QUESTIONS.
  