| 2021-11-10 14:20:25 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | |
| | 1) THE PROPOSED STRUCTURE IS CLASSIFIED AS A STORAGE |
| | OCCUPANCY PER THE NFPA 101 LIFE SAFETY CODE. |
| | |
| | THERE ARE 3 DOORS THAT MAY SERVE AND FUNCTION AS THE |
| | REQUIRED EXIT. |
| | |
| | PER NFPA 101 CH 42 STORAGE OCCUPANCIES |
| | |
| | 42.1.1.5 STORAGE OCCUPANCIES SHALL INCLUDE ALL |
| | BUILDINGS OR STRUCTURES |
| | USED PRIMARILY FOR THE STORAGE OR SHELTERING OF GOODS, |
| | MERCHANDISE, |
| | PRODUCTS, OR VEHICLES. |
| | |
| | 42.2.10 MARKING OF MEANS OF EGRESS. MEANS OF EGRESS |
| | SHALL HAVE |
| | SIGNS IN ACCORDANCE WITH SECTION 7.10. |
| | |
| | 7.10.1.2 EXITS. |
| | 7.10.1.2.1* EXITS, OTHER THAN MAIN EXTERIOR EXIT DOORS |
| | THAT OBVIOUSLY |
| | AND CLEARLY ARE IDENTIFIABLE AS EXITS, SHALL BE MARKED |
| | BY AN APPROVED |
| | SIGN THAT IS READILY VISIBLE FROM ANY DIRECTION OF EXIT |
| | ACCESS. |
| | |
| | PLEASE INDICATE WHICH DOOR IS THE REQUIRED EXIT AND |
| | MARK IT ACCORDINGLY WITH AN EXIT SIGN. |
| | |
| | |
| | 2) THE LOCKS ON THE REQUIRED EXIT DOOR SHALL COMPLY |
| | WITH NFPA 101 |
| | |
| | 42.2.2.2.1 DOORS COMPLYING WITH 7.2.1 SHALL BE |
| | PERMITTED. |
| | |
| | 7.2.1.5.1 DOOR LEAVES SHALL BE ARRANGED TO BE OPENED |
| | READILY FROM THE |
| | EGRESS SIDE WHENEVER THE BUILDING IS OCCUPIED. |
| | |
| | 7.2.1.5.3 LOCKS, IF PROVIDED, SHALL NOT REQUIRE THE USE |
| | OF A KEY, A TOOL, |
| | OR SPECIAL KNOWLEDGE OR EFFORT FOR OPERATION FROM THE |
| | EGRESS SIDE. |
| | |
| | PLEASE PROVIDE THE REQUIRED EXIT DOOR WITH A COMPLIANT |
| | LOCK IF INSTALLED. |
| | |
| | |
| | |
| | 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |
| | 561-804-4709 |