| Plan Review Notes For Permit 21060282 |
| Permit Number |
21060282 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2021-07-08 12:48:06 | METAL BUILDING | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected] | | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | | AMENDMENTS | | | | | | CORRECTIONS NEEDED - | | | 1) PLEASE PROVIDE A SURVEY SHOWING THE LOCATION OF THE | | | METAL BUILDING - SHOW SETBACKS FROM THE PROPERTY LINES | | | AND EXISTING BUILDINGS. FBC WPB 107.2.5 | | | 2) PLEASE SHOW THE INTENDED USE FOR THE BUILDING. FBC | | | CHAPTER 3 | | | 3) PLEASE PROVIDE COMPLETE COPIES OF THE PRODUCT | | | APPROVALS LISTED ON THE DRAWINGS. FBC WPB 107.1 | | | 4) WIND DESIGN DATA SHOWN ON DRAWING SHEET 1 OF 3 SHOWS | | | WIND DESIGNED AS AN "ENCLOSED" BUILDING YET THERE ARE | | | OPENINGS WITH NO COMPONENTS - PLEASE REEVALUATE THE | | | WIND DESIGN DATA. FBC 1609 | | | 5) PLEASE SHOW THE CODE VERSION USED FOR THE DESIGN ON | | | THE DRAWINGS - SHOULD BE (2020 FBC) | | | |
|