| 2021-06-15 16:16:39 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1 |
| | WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL |
| | MANUAL REVISED 2017 |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 |
| | 7TH EDITION |
| | FBC EX = FLORIDA EXISTING BUILDING CODE 2020 7TH |
| | EDITION |
| | FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION |
| | FAC= FLORIDA ADMINISTRATIVE CODE |
| | FS = FLORIDA STATUTES |
| | |
| | |
| | 1ST REVIEW |
| | |
| | PLEASE NOTE THAT WHEN SCANNED DRAWINGS ARE SUBMITTED |
| | WITH CONTRACTOR'S PRINTED NAME, SIGNATURE AND LICENSE |
| | NUMBER IN ACCORDANCE WITH WPB FBC 107.3.4.3, A PAPER |
| | PLAN WITH WET SIGNATURE SHALL BE PROVIDED TO THE |
| | BUILDING DEPARTMENT FOR HARD RECORD FILE PRIOR TO |
| | ISSUANCE OF A PERMIT. |
| | |
| | PLUMBING COMMENTS: DENIED |
| | |
| | PER WPB FBC 104.1, A PLUMBING SUB-PERMIT APPLICATION |
| | SHALL BE SUBMITTED FOR THIS PROJECT BY A LICENSED |
| | PLUMBING CONTRACTOR. |
| | |
| | 1.AS THE PLANS ARE NOT SIGNED AND SEALED BY A |
| | PROFESSIONAL ENGINEER OR ARCHITECT, A SEPARATE PLUMBING |
| | PLAN IN ACCORDANCE WITH WPB FBC 107.3.4.3 SHALL BEAR |
| | THE PRINTED NAME, THE SIGNATURE AND THE CERTIFICATION |
| | NUMBER OF THE DESIGNER WHO SHALL BE A CONTRACTOR |
| | LICENSED IN THE PLUMBING TRADE. |
| | |
| | A.PER WPB FBC 107.2.1, PROVIDE A KITCHEN FLOOR PLAN |
| | NAMED PLUMBING PLAN: PROVIDE THE FOLLOWING: |
| | 1) INDICATE ACTUAL PLUMBING SCOPE OF WORK I.E. REPLACE |
| | EXISTING SINK WITH NEW, MAKE PLUMBING CONNECTIONS TO |
| | SINK, DISHWASHER AND REFRIGERATOR ICE MAKER. |
| | 2 )PROVIDE NOTE, "ALL WORK TO COMPLY WITH FLORIDA |
| | PLUMBING CODE 2020 7TH EDITION." |
| | 3) PROVIDE NOTE, "PROVIDE WATER HAMMER ARRESTORS PER |
| | FLORIDA PLUMBING CODE 604.9" |
| | 4) PROVIDE NOTE, "CONNECT DISHWASHER WASTE DIRECTLY TO |
| | A WYE BRANCH FITTING ON THE TAILPIECE OF THE KITCHEN |
| | SINK, DIRECTLY TO THE DISHWASHER CONNECTION OF A FOOD |
| | WASTE DISPOSER, OR THROUGH AN AIR BREAK TO A STANDPIPE. |
| | THE WASTE LINE OF A RESIDENTIAL DISHWASHER SHALL RISE |
| | AND BE SECURELY FASTENED TO THE UNDERSIDE OF THE SINK |
| | RIM OR COUNTER TOP PER FLORIDA PLUMBING CODE 604.9" |
| | |
| | |
| | END OF COMMENTS. |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED |
| | AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS. |
| | |
| | |
| | |
| | JERALD SMITH |
| | PLUMBING PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | EMAIL [email protected] |
| | MOBILE 561-246-0882 |
| | PLEASE NOTE THAT I TYPICALLY WORK ON TUESDAYS AND |
| | THURSDAYS |
| | |
| | 21060265 1701 S FLAGLER DR # 1208 |