| 2021-10-20 12:30:47 | 3RD REVIEW FBC-2020 PLUMBING |
| | PERMIT- 21060251 |
| | 10/20/2021 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 |
| | FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| | 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS- DENIED. |
| | |
| | 1) THE ITEMS LISTED BELOW WERE SUBMITTED WITHOUT |
| | APPROVAL STAMPS BY EITHER THE ARCHITECT OR ENGINEER OF |
| | RECORD: |
| | A) OIL/SAND INTERCEPTOR |
| | B) RECLAIM TANKS |
| | C) WASH EQUIPMENT |
| | D) VACUUM EQUIPMENT |
| | E) AIR COMPRESSOR |
| | PLEASE NOTE THAT THE APPROVAL STAMPS ON THE INTERCEPTOR |
| | AND RECLAIM TANKS WERE NOT SIGNED BY EITHER THE |
| | ARCHITECT OR ENGINEER OF RECORD- SECTION 107.3.4 WPB. |
| | REFER TO SECTIONS 107.1 AND 107.3.4.1: THE ITEMS ABOVE |
| | MAY BE DEFERRED HOWEVER IT WOULD BE HELPFUL TO PROVIDE |
| | A MASTER LIST ON THE PLAN OF ALL DEFERRED SUBMITTALS. |
| | |
| | 2) SUBMITTAL ITEMS LISTED BELOW WERE REQUESTED BUT NOT |
| | SUBMITTED: |
| | A) RECLAIM AND OIL/SAND INTERCEPTOR TANK HEAVY DUTY |
| | TRAFFIC LIDS |
| | B) WATER HEATER |
| | C) EXPANSION TANK |
| | D) RECIRCULATION PUMP |
| | E) MIXING VALVES |
| | REFER TO SECTIONS 107.1 AND 107.3.4.1: THE ITEMS ABOVE |
| | MAY BE DEFERRED HOWEVER IT WOULD BE HELPFUL TO PROVIDE |
| | A MASTER LIST ON THE PLAN OF ALL DEFERRED SUBMITTALS. |
| | |
| | 3) SHEETS P1.1 & PR7.4: THE PLANS SHOW RECLAIM TANKS |
| | WITH TWO MANHOLE OPENINGS HOWEVER THE SHOP DRAWINGS |
| | SHOW TANKS WITH TWO OPENINGS. WHICH ARE THE TANKS TO BE |
| | INSTALLED? |
| | |
| | 4) PR7.4: AS NOTED IN COMMENT #2, HEAVY DUTY TANK LID |
| | COVERS WERE NOT SUBMITTED. PLEASE NOTE THE LIDS SHALL |
| | BE HS-20 AASHTO RATED. THE LIDS MAY BE DEFERRED AND |
| | ADDED TO THE MASTER LIST. |
| | |
| | 5) BASED ON THE SUBMITTED SHOP DRAWINGS, THE VACUUM |
| | SYSTEM REQUIRES STRUCTURAL ENGINEERING FOR INSTALLATION |
| | HOWEVER THE ENGINEERING HAS NOT BEEN PROVIDED. PLEASE |
| | PROVIDE THE ENGINEERING OR INDICATE IT WILL BE |
| | DEFERRED- SECTION 107.3.4.1 WPB. PLEASE NOTE THAT THE |
| | STRUCTURAL ENGINEERING SHALL INCLUDE WIND LOAD |
| | ENGINEERING FOR TIE DOWN OF EXPOSED EQUIPMENT- SECTION |
| | 301.15 FBC M. |
| | |
| | 6) P5.1: PLEASE CORRECT THE NOTE INDICATING 110-DEGREE |
| | HOT WATER SUPPLY TO THE LAVATORIES FROM THE MIXING |
| | VALVE- SEE DEFINITIONS OF HOT AND TEMPERED WATER. |
| | TEMPERED WATER IS REQUIRED AT THE LAVS AND IS DEFINED |
| | AS WATER WITH TEMPERATURE BETWEEN 85-110 DEGREES F. HOT |
| | WATER IS EQUAL TO OR GREATER THAT 110. |
| | |
| | 7) P2.1 & PR7.2: THE MAN POTABLE WATER SERVICE BACKFLOW |
| | PREVENTER IS INDICATED AS BF-1 ON P2.1 & BF-2 ON PR7.2. |
| | PLEASE SEE TABLE 608.1 FBC P AND PROVIDE A BACK FLOW |
| | PREVENTER RATED FOR HIGH HAZARD. |
| | |
| | 8) P3.1: PLEASE PROVIDE THE GPM DRAINAGE FLOW FOR EACH |
| | ZONE OR AT EACH RD SHOWN IN THE ISO- TABLE 1106.3 FBC |
| | P. |
| | |
| | 9) A8.1: THE SCUPPER DETAIL DOES NOT APPEAR IN |
| | COMPLIANCE WITH SECTION 1503.4..2.1 FBC B WHICH |
| | INDICATES THE SCUPPERS SHALL BE PLACED IN THE PARAPET |
| | WALLS NOT LESS THAN 2 INCHES NOR MORE THAN 4 INCHES |
| | ABOVE THE ROOF COVERING. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL/PLUMBING PLANS EXAMINER |