| 2021-09-16 12:58:50 | NEW COMMERCIAL BUILDING |
| | REVIEWED BY ROGER MCPHERSON |
| | 561-805-6716 |
| | [email protected]. |
| | CODE USED FOR REVIEW - 2020 FBC WITH 2017 WPB CHAPTER 1 |
| | AMENDMENT |
| | |
| | CORRECTIONS NEEDED - |
| | 1) DRAWING A1.0 STATES THAT THE BUILDING IS IN A FLOOD |
| | ZONE "X" - SURVEY PROVIDED SHOWS THE BUILDING IN A |
| | FLOOD ZONE (AE12.70) AND (X) - PLEASE REVISE THE |
| | DRAWING. |
| | |
| | 2) PLEASE SHOW THE "LOWEST FLOOR" ELEVATION USING |
| | "NAVD" ON THE DRAWINGS FBC 1612.1 |
| | |
| | 3) PLEASE SHOW THE ACCESSIBLE RESTROOM MIRROR |
| | DIMENSIONS FROM THE FINISHED FLOOR TO THE "REFLECTING |
| | SURFACE" TO COMPLY WITH FBC 603.3 MIRRORS. |
| | MIRRORS LOCATED ABOVE LAVATORIES OR COUNTERTOPS SHALL |
| | BE INSTALLED WITH THE BOTTOM EDGE OF THE REFLECTING |
| | SURFACE 40 INCHES (1015 MM) MAXIMUM ABOVE THE FINISH |
| | FLOOR OR GROUND. |
| | |
| | 4) PLEASE PROVIDE COMPLETE MIAMI DADE OR FLORIDA STATE |
| | PRODUCT APPROVALS FOR THE EXTERIOR DOORS - REVIEWED AND |
| | MARKED APPROVED BY THE BUILDING DESIGNER OF RECORD FBC |
| | WPB 107.3.4 |
| | |
| | 5) PRODUCT APPROVAL FOR THE FLAT DECK ROOFING (FL16730 |
| | ) = NEED TO CHOOSE A ROOFING SYSTEM IN THE PRODUCT |
| | APPROVAL THAT SHOWS THE REQUIRED WIND DESIGN PRESSURE - |
| | PLEASE CIRCLE THE ROOFING SYSTEM TO BE USED IN THE |
| | PRODUCT APPROVAL - IF NEEDED PLEASE PROVIDE ADDITIONAL |
| | ATTACHMENT DETAILS FROM AN ARCHITECT OR ENGINEER FOR |
| | THE ROOF ZONES 2 AND 3 WHICH MAY REQUIRE A HIGHER WIND |
| | PRESSURE THEN THE CHOSEN ROOFING SYSTEM - SEE NOTES ON |
| | THE PRODUCT APPROVAL. |
| | |
| | 6) PLEASE PROVIDE THE FRONT PAGES FOR THE FLORIDA STATE |
| | OR MIAMI DADE PRODUCT APPROVALS - THE ONLY FRONT PAGE |
| | PROVIDED IS FOR THE LOUVERS - PLEASE PROVIDE THE FRONT |
| | PAGES FOR ALL OTHER PRODUCT APPROVALS. |
| | |
| | |
| | |