| 2021-08-02 14:31:36 | NEW COMMERCIAL BUILDING |
| | REVIEWED BY ROGER MCPHERSON |
| | 561-805-6716 |
| | [email protected]. |
| | CODE USED FOR REVIEW - 2020 FBC WITH 2017 WPB CHAPTER 1 |
| | AMENDMENT |
| | |
| | CORRECTIONS NEEDED - |
| | 1) PALM BEACH COUNTY FLOOD ZONE MAP SHOWS THE PROPERTY |
| | IS IN A FLOOD ZONE AE12 - PLEASE PROVIDE AN UP DATED |
| | SURVEY BASED ON THE LATEST FIRM USING NAVD SHOWING THE |
| | PROPOSED BUILDING FOOT PRINT AND THE FLOOD ZONE |
| | DELINEATION LINES. |
| | 2) PLEASE PROVIDE A SOIL REPORT (GEOTECHNICAL REPORT). |
| | 3) PLEASE SHOW THE ACCESSIBLE RESTROOM MIRROR |
| | DIMENSIONS FROM THE FINISHED FLOOR TO THE REFLECTING |
| | SURFACE TO COMPLY WITH FBC 603.3 MIRRORS. |
| | MIRRORS LOCATED ABOVE LAVATORIES OR COUNTERTOPS SHALL |
| | BE INSTALLED WITH THE BOTTOM EDGE OF THE REFLECTING |
| | SURFACE 40 INCHES (1015 MM) MAXIMUM ABOVE THE FINISH |
| | FLOOR OR GROUND. |
| | 4) PLEASE SHOW THE DIMENSIONS FOR THE TOILET REAR GRAB |
| | BAR FROM THE CENTER OF THE TOILET PER FBC 604.5.2 REAR |
| | WALL. |
| | THE REAR WALL GRAB BAR SHALL BE 36 INCHES (915 MM) LONG |
| | MINIMUM AND EXTEND FROM THE CENTERLINE OF THE WATER |
| | CLOSET 12 INCHES (305 MM) MINIMUM ON ONE SIDE AND 24 |
| | INCHES (610 MM) MINIMUM ON THE OTHER SIDE. |
| | 5) PLEASE PROVIDE COMPLETE MIAMI DADE OR FLORIDA STATE |
| | PRODUCT APPROVALS FOR THE EXTERIOR WINDOWS, DOORS, |
| | LOUVERS AND ROOFING SYSTEM. |
| | 6) ALL PRODUCT APPROVALS, SHOP DRAWINGS NEED TO BE |
| | REVIEWED AND MARKED APPROVED BY THE DESIGNER OF RECORD |
| | FBC WPB 107.3.4 |
| | 7) SEPARATE PERMITS ARE REQUIRED FOR DUMPSTER |
| | ENCLOSURE, PARKING LOT, SIGNS - PLEASE ACKNOWLEDGE |
| | THIS. |