| 2021-11-09 13:12:46 | PLAN REVIEW BUILDING |
| | |
| | CHRISTOPHER S. THROOP, C.B.O., CFM |
| | PLANS EXAMINER II PX3169/SFP306 |
| | INSPECTOR BN4338 |
| | BUILDING OFFICIAL BU1635 |
| | ASFPM CERTIFIED FLOODPLAIN MANAGER US-21-11935 |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | CITY OF WEST PALM BEACH |
| | (561) 805-6726 |
| | [email protected] |
| | |
| | CODES IN EFFECT: |
| | 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST |
| | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| | CHAPTER 1 ADMINISTRATION |
| | 2017 NEC |
| | |
| | 3RD REVIEW |
| | |
| | RESULTS: DENIED |
| | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| | |
| | PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED |
| | SATISFACTORILY ARE MARKED AS CORRECTED. |
| | PREVIOUS COMMENTS THAT HAVE NOT BEEN ADDRESSED |
| | SATISFACTORILY MAY HAVE ADDITIONAL COMMENTS IN |
| | PARENTHESES. ANY NEW COMMENT WILL BE LISTED AFTER |
| | PREVIOUS COMMENTS. |
| | |
| | |
| | |
| | 1. PROVIDE A SITE PLAN W/BOUNDRY LINE SURVEY (NOT |
| | ADDRESSED) |
| | 107.2.5 SITE PLAN. THE CONSTRUCTION DOCUMENTS SUBMITTED |
| | WITH THE APPLICATION FOR PERMIT SHALL BE ACCOMPANIED BY |
| | A SITE PLAN SHOWING TO SCALE THE SIZE AND LOCATION OF |
| | NEW CONSTRUCTION AND EXISTING STRUCTURES ON THE |
| | SITE,... AND IT SHALL BE DRAWN IN ACCORDANCE WITH AN |
| | ACCURATE AND INCLUDED BOUNDARY LINE SURVEY. |
| | |
| | 2. PROVIDE A SITE DRAINAGE PLAN. (NOT ADDRESSED) |
| | FBC R401.3 SITE DRAINAGE |
| | PROVIDE A SITE DRAINAGE PLAN SHOWING COMPLIANCE WITH |
| | FBC R401.3 DRAINAGE. |
| | |
| | 3. REF: PROJECT DATA, PLAN PAGE A.01 FOR THE FOLLOWING: |
| | CORRECT BLDG CODE TO 2020 FBC 7TH ED. (NOT ADDRESSED) |
| | |
| | 4. PROVIDE PRODUCT APPROVALS FOR WINDOWS AND DOORS. |
| | CORRECTED |
| | FBC 107.3.4 PROVIDE PRODUCT APPROVALS FOR THOSE |
| | PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED |
| | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. |
| | |
| | 5. PROVIDE ROOF SHEATHING FASTENER SCHEDULE FOR ROOF |
| | ZONES 1,2 & 3 BASED ON THE DESIGN PRESSURES. (NOT |
| | ADDRESSED) |
| | TABLE R301.2.1.2 WINDBORNE DEBRIS PROTECTION FASTENING |
| | SCHEDULE FOR WOOD STRUCTURAL PANELS. |
| | |
| | 6. PROVIDE THE ICC-ES REPORT FOR THE PROPOSED SPRAY |
| | FOAM INSULATION. PROVIDE A COPY TO CITY INSPECTOR FOR |
| | INSPECTION. (NOT ADDRESSED) |
| | |
| | NEW COMMENTS: |
| | |
| | 7. THE DESIGN PRESSURES OF THE WINDOWS AND DOORS |
| | SUBMITTED FOR REVIEW DO NOT MEET OR EXCEED THE DESIGN |
| | PRESSURES ON THE COMPONENETS AND CLADDING EXTERNAL |
| | PRESSURE LOADS ON PLAN PAG. S-003. |
| | THE DESIGN PRESSURES APPEAR HIGH WHEN COMPARED TO THE |
| | DESIGN PRESSURES IN FBCR TABLE R301.2(2). DESIGNER |
| | SHALL RE-VISIT DESIGN PRESSURES OR SUBMIT PRODUCT |
| | APPROVALS WITH DESIGN PRESSURES THAT COMPLY WITH THE |
| | DESIGNERS CALCULATIONS. |
| | |
| | 8. THE ADDRESS 199 ALMERIA RD IS FOR THE MAIN DWELLING |
| | UNIT. 2 NEW ADDESSES HAVE BEEN ASSIGNED TO THE ACCESS. |
| | STRUCTURE. 201 ALMERIA RD IS FOR THE EXISTING |
| | DOWNSTAIRS UNIT. 203 ALMERIA RD IS FOR THE NEW 2ND |
| | FLOOR ADDITION. |
| | WORK IS PROPOSED ON EACH LEVEL/ADDRESS. |
| | ADDRESS ON PLANS NEEDS TO BE CHANGED TO 201 AND 203 |
| | ALMERIA RD. |
| | |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | |
| | WHEN RESUBMITING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |