Plan Review Notes
Plan Review Notes For Permit 21060240
Permit Number 21060240
Review Stop P
Sequence Number 1
Notes
Date Text
2021-06-23 11:14:2106/23/21 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. ON SHEET P1.0;
 A. THE LINE COMING INTO THE FIRST FLOOR FEEDING THE
 KITCHEN AND WASHING MACHINE CANNOT BE ON AN AIR
 ADMITTANCE VALVE AND SHALL BE VENTED THROUGH THE ROOF,
 WITHIN EACH PLUMBING SYSTEM, NOT LESS THAN ONE STACK
 VENT OR A VENT STACK SHALL EXTEND OUTDOORS TO THE OPEN
 AIR PER THE 2020 FBC P3114.7 VENT REQUIRED.
  
 B. THE BATHROOMS HAVE THE TOILET IN A WASTE STACK VENT
 AD ARE NOT ALLOWED TO RECEIVE THE DISCHARGE OF WATER
 CLOSET PER THE 2020 FBC P3109.2 STACK INSTALLATION.
 PLEASE SHOW SEPARATE BATHROOM GROUPS.
  
 C. THERE IS A SINK IN THE STORAGE ROOM ON THE FIRST
 FLOOR, THE COMMENT A WILL ALSO APPLY TO IT. IT IS NOT
 SHOWN IN THE LAYOUT OF THE BUILDING. IS IT NEW OR
 EXISTING? PLEASE REMOVE OR CLARIFY PER THE P3109.2
 STACK INSTALLATION?
  
 D. PLEASE PROVIDE A SEPARATE SHUTOFF VALVE FOR EACH
 UNIT ON EACH FLOOR PER THE 2020 FBC P2903.9.1 SERVICE
 VALVE.
  
 2. ON SHEET A.02, IT SAYS THE KITCHENETTE, REMOVE PER
 ZONING OR CLARIFY PER THE WPB AMENDMENTS TO FBC
 SEC.107.2.1.
  
 3. IF APPLICABLE TO PLUMBING, PLEASE SUBMIT A SLAB
 REPAIR DETAIL FOR REVIEW. SHOW THE WIDTH OF THE REPAIR,
 THE MINIMUM THICKNESS OF THE CONCRETE TO BE REPLACED,
 AND THE PSI OF THE CONCRETE. SHOW THE SIZE AND LENGTH
 OF THE DOWELS, THE MINIMUM EMBEDMENT DEPTH INTO THE
 EXISTING SLAB, AND THE SPACING OF THE DOWELS IN THE
 CENTER. THE REPAIR SHALL ALSO INCLUDE TERMITE TREATMENT
 OF THE SOIL AND THE REQUIRED VAPOR BARRIER OVER THE
 SOIL. A COPY OF THE TERMITE CERTIFICATE SHALL BE ONSITE
 FOR A FINAL INSPECTION.
  
 4. THESE ARE MULTI-FAMILY DWELLINGS, AND WATER USERS
 WILL BE REQUIRED TO INSTALL A BACKFLOW PREVENTION
 ASSEMBLY AT THE POINT OF DELIVERY. THE TYPE OF BACKFLOW
 ASSEMBLY REQUIRED WILL BE DEPENDENT UPON THE DEGREE OF
 HAZARD POSED BY THE WATER USER. A REDUCED PRESSURE ZONE
 BACKFLOW DEVICE WILL BE NEEDED FOR THE WATER METER PER
 THE CITY OF WEST PALM CROSS UTILITIES DEPARTMENT AND
 THEIR CONNECTION CONTROL PROGRAM.
  
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND, WILL HELP EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved