| Date |
Text |
| 2021-06-23 11:14:21 | 06/23/21 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS |
| | |
| | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| | TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| | |
| | 1. ON SHEET P1.0; |
| | A. THE LINE COMING INTO THE FIRST FLOOR FEEDING THE |
| | KITCHEN AND WASHING MACHINE CANNOT BE ON AN AIR |
| | ADMITTANCE VALVE AND SHALL BE VENTED THROUGH THE ROOF, |
| | WITHIN EACH PLUMBING SYSTEM, NOT LESS THAN ONE STACK |
| | VENT OR A VENT STACK SHALL EXTEND OUTDOORS TO THE OPEN |
| | AIR PER THE 2020 FBC P3114.7 VENT REQUIRED. |
| | |
| | B. THE BATHROOMS HAVE THE TOILET IN A WASTE STACK VENT |
| | AD ARE NOT ALLOWED TO RECEIVE THE DISCHARGE OF WATER |
| | CLOSET PER THE 2020 FBC P3109.2 STACK INSTALLATION. |
| | PLEASE SHOW SEPARATE BATHROOM GROUPS. |
| | |
| | C. THERE IS A SINK IN THE STORAGE ROOM ON THE FIRST |
| | FLOOR, THE COMMENT A WILL ALSO APPLY TO IT. IT IS NOT |
| | SHOWN IN THE LAYOUT OF THE BUILDING. IS IT NEW OR |
| | EXISTING? PLEASE REMOVE OR CLARIFY PER THE P3109.2 |
| | STACK INSTALLATION? |
| | |
| | D. PLEASE PROVIDE A SEPARATE SHUTOFF VALVE FOR EACH |
| | UNIT ON EACH FLOOR PER THE 2020 FBC P2903.9.1 SERVICE |
| | VALVE. |
| | |
| | 2. ON SHEET A.02, IT SAYS THE KITCHENETTE, REMOVE PER |
| | ZONING OR CLARIFY PER THE WPB AMENDMENTS TO FBC |
| | SEC.107.2.1. |
| | |
| | 3. IF APPLICABLE TO PLUMBING, PLEASE SUBMIT A SLAB |
| | REPAIR DETAIL FOR REVIEW. SHOW THE WIDTH OF THE REPAIR, |
| | THE MINIMUM THICKNESS OF THE CONCRETE TO BE REPLACED, |
| | AND THE PSI OF THE CONCRETE. SHOW THE SIZE AND LENGTH |
| | OF THE DOWELS, THE MINIMUM EMBEDMENT DEPTH INTO THE |
| | EXISTING SLAB, AND THE SPACING OF THE DOWELS IN THE |
| | CENTER. THE REPAIR SHALL ALSO INCLUDE TERMITE TREATMENT |
| | OF THE SOIL AND THE REQUIRED VAPOR BARRIER OVER THE |
| | SOIL. A COPY OF THE TERMITE CERTIFICATE SHALL BE ONSITE |
| | FOR A FINAL INSPECTION. |
| | |
| | 4. THESE ARE MULTI-FAMILY DWELLINGS, AND WATER USERS |
| | WILL BE REQUIRED TO INSTALL A BACKFLOW PREVENTION |
| | ASSEMBLY AT THE POINT OF DELIVERY. THE TYPE OF BACKFLOW |
| | ASSEMBLY REQUIRED WILL BE DEPENDENT UPON THE DEGREE OF |
| | HAZARD POSED BY THE WATER USER. A REDUCED PRESSURE ZONE |
| | BACKFLOW DEVICE WILL BE NEEDED FOR THE WATER METER PER |
| | THE CITY OF WEST PALM CROSS UTILITIES DEPARTMENT AND |
| | THEIR CONNECTION CONTROL PROGRAM. |
| | |
| | WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES. |
| | A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND, WILL HELP EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA |
| | |
| | LUIS A. CRESPO |
| | PLUMBING PLAN EXAMINER / INSPECTOR |
| | EMAIL: [email protected] OFFICE: 561 805-6720 |
| | |
| | |