Plan Review Notes
Plan Review Notes For Permit 21060240
Permit Number 21060240
Review Stop M
Sequence Number 1
Notes
Date Text
2021-06-16 12:57:371ST REVIEW FBC-2020 MECHANICAL
 PERMIT-21060240
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE PROVIDE EQUIPMENT SIZING CALCULATIONS. FBC EC
 R403.7
  
 2) SHEET M2.0: IN THE INDOOR UNIT SCHEDULE PLEASE LABEL
 THE INDOOR UNITS TO RELATE TO THE SYSTEM DESIGN DRAWING
 ON SHEET M1.0 FBC 107.2.1
  
 3) PLEASE SHOW THE RETURN AIR PATH FROM THE HABITABLE
 ROOMS BACK TO THE FCU?S. FBC RES M1602.3
  
 4) PLEASE SHOW THE DRYER DUCT WORK AND THE TERMINATION
 LOCATION. FBC RES M1502
  
 5) PLEASE PROVIDE THE ANCHORAGE DETAILS FOR THE AC-1.
 FBC RES M1307.2
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  