| 2021-06-23 11:57:08 | 06/23/21 1ST GAS REVIEW**DENIED** WITH COMMENTS |
| | |
| | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| | TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| | |
| | 1. THE MAIN GAS IS CONNECTED TO UTILITIES TO THE METER, |
| | BUT THE ONE-INCH LINE GOES TO THE GENERATOR AND THEN TO |
| | THE GAS METER. PLEASE SHOW LINE TO THE GAS METER AND |
| | THEN TO GENERATOR AND SIZE CORRECTLY PER THE WPB |
| | AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS. |
| | |
| | 2. THE ELECTRICAL PLAN SHOWS A GAS HEATER AND AN |
| | ELECTRICAL. PLEASE CORRECT AND CLARIFY WHICH TYPE OF |
| | APPLIANCE WILL BE USED PER THE WPB AMENDMENTS TO THE |
| | FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | 3. PLEASE SHOW A CAP IN FRONT OF THE SHUT OFF VALVE PER |
| | THE AJH OF THE WEST PALM BEACH PLUMBING DEPARTMENT FOR |
| | FUTURE GENERATORS. |
| | |
| | 4. ON SHEET P1.0; |
| | A. THE DEATH OF PIPE MAY NOT BE AN ACTUAL NUMBER AS A |
| | MINIMUM IS 12? IN MOST CASES. |
| | |
| | B. THE GAS LINES TO THE HEATER ARE SHOWN UNDER THE SLAB |
| | AND NOT ALLOWED UNLESS IT IS A CRAWL SPACE. PLEASE MOVE |
| | OR CLARIFY PIPE PER THE WPB AMENDMENTS ROUTING TO THE |
| | FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | 5. PLEASE CLEARLY SHOW THE LENGTH OF ALL CUT SECTIONS |
| | OF PIPE PER 2020 FBC RES FOR THE ISOMETRIC DRAWING. |
| | SECS. G2413.4.1, G2413.4.2. |
| | |
| | 6. SHOW THE TYPE OF PIPE MATERIAL BEING INSTALLED, ALL |
| | PIPE SIZES, AND THE CORRESPONDING EHD NUMBER OF THE |
| | CORRUGATED STAINLESS-STEEL TUBING (IF APPLICABLE) FOR |
| | EACH PIPE SIZE PER THE WPB AMENDMENTS TO THE FBC |
| | SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | 7. SUBMIT MANUFACTURER?S SPECIFICATIONS FOR THE |
| | PRESSURE REGULATORS. REGULATORS INSTALLED ON THE |
| | EXTERIOR OF THE BUILDING SHALL BE APPROVED FOR OUTDOOR |
| | INSTALLATION PER THE 2020 FBC RES. SEC. G2421.1. |
| | |
| | 8. TYPE OF GAS (LP OR NATURAL) PER THE WPB AMENDMENTS |
| | TO THE FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION |
| | DOCUMENTS. |
| | |
| | 9. SHOW THE DISTANCE FROM THE POINT OF DELIVERY (GAS |
| | METER / MP REGULATOR / LP TANK) TO THE MOST REMOTE |
| | OUTLET IN THE BUILDING AND/OR SYSTEM PER THE 2020 FBC |
| | RES. SEC. G2413.4.1. |
| | |
| | 10. INDICATE THE SYSTEM'S DELIVERY PRESSURE (PSI) ON |
| | THE PLAN PER THE 2020 FBC RES. SEC. G2413.2. |
| | |
| | 11. PLEASE SUBMIT MANUFACTURER?S SPECIFICATION |
| | SHEETS/INSTALLATION MANUAL FOR HEATER EQUIPMENT TO |
| | VERIFY COMPLIANCE WITH 2020 FBC RES. SEC. G2408.1. |
| | |
| | 12. PLEASE SUBMIT THE SIZING TABLE USED IN THE DESIGN |
| | FOR THE GAS SYSTEM OR PLACE A NOTE ON PLANS LISTING THE |
| | SIZING TABLES FROM GAS CODES OR ANOTHER STANDARD USED |
| | IN THIS SYSTEM'S DESIGN PER THE 2020 FBC RES. SEC. |
| | G2413.3. |
| | |
| | 13. PLEASE SHOW ALL UNIONS IN FRONT OF THE REGULATOR |
| | ONE INCH OF EITHER SIDE PER THE 2020 FBC RES. SEC |
| | G2421.2. |
| | |
| | 14. A REGULATOR IS REQUIRED TO BRING THE SYSTEM DOWN TO |
| | 10.5 INCH WC. PLEASE SUBMIT THE MANUFACTURER?S |
| | SPECIFICATIONS FOR THE PRESSURE REGULATORS PER THE 2020 |
| | FBC RES. SEC. G2421.1. |
| | |
| | 15. SHOW DRIP LEG ON EQUIPMENT INSTALLED PER THE 2020 |
| | FBC RES. SEC. G2419.2. |
| | |
| | WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES. |
| | A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND, WILL HELP EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA |
| | |
| | LUIS A. CRESPO |
| | PLUMBING PLAN EXAMINER / INSPECTOR |
| | EMAIL: [email protected] OFFICE: 561 805-6720 |
| | |