Plan Review Notes
Plan Review Notes For Permit 21060240
Permit Number 21060240
Review Stop G
Sequence Number 1
Notes
Date Text
2021-06-23 11:57:0806/23/21 1ST GAS REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. THE MAIN GAS IS CONNECTED TO UTILITIES TO THE METER,
 BUT THE ONE-INCH LINE GOES TO THE GENERATOR AND THEN TO
 THE GAS METER. PLEASE SHOW LINE TO THE GAS METER AND
 THEN TO GENERATOR AND SIZE CORRECTLY PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 2. THE ELECTRICAL PLAN SHOWS A GAS HEATER AND AN
 ELECTRICAL. PLEASE CORRECT AND CLARIFY WHICH TYPE OF
 APPLIANCE WILL BE USED PER THE WPB AMENDMENTS TO THE
 FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 3. PLEASE SHOW A CAP IN FRONT OF THE SHUT OFF VALVE PER
 THE AJH OF THE WEST PALM BEACH PLUMBING DEPARTMENT FOR
 FUTURE GENERATORS.
  
 4. ON SHEET P1.0;
 A. THE DEATH OF PIPE MAY NOT BE AN ACTUAL NUMBER AS A
 MINIMUM IS 12? IN MOST CASES.
  
 B. THE GAS LINES TO THE HEATER ARE SHOWN UNDER THE SLAB
 AND NOT ALLOWED UNLESS IT IS A CRAWL SPACE. PLEASE MOVE
 OR CLARIFY PIPE PER THE WPB AMENDMENTS ROUTING TO THE
 FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 5. PLEASE CLEARLY SHOW THE LENGTH OF ALL CUT SECTIONS
 OF PIPE PER 2020 FBC RES FOR THE ISOMETRIC DRAWING.
 SECS. G2413.4.1, G2413.4.2.
  
 6. SHOW THE TYPE OF PIPE MATERIAL BEING INSTALLED, ALL
 PIPE SIZES, AND THE CORRESPONDING EHD NUMBER OF THE
 CORRUGATED STAINLESS-STEEL TUBING (IF APPLICABLE) FOR
 EACH PIPE SIZE PER THE WPB AMENDMENTS TO THE FBC
 SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 7. SUBMIT MANUFACTURER?S SPECIFICATIONS FOR THE
 PRESSURE REGULATORS. REGULATORS INSTALLED ON THE
 EXTERIOR OF THE BUILDING SHALL BE APPROVED FOR OUTDOOR
 INSTALLATION PER THE 2020 FBC RES. SEC. G2421.1.
  
 8. TYPE OF GAS (LP OR NATURAL) PER THE WPB AMENDMENTS
 TO THE FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS.
  
 9. SHOW THE DISTANCE FROM THE POINT OF DELIVERY (GAS
 METER / MP REGULATOR / LP TANK) TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER THE 2020 FBC
 RES. SEC. G2413.4.1.
  
 10. INDICATE THE SYSTEM'S DELIVERY PRESSURE (PSI) ON
 THE PLAN PER THE 2020 FBC RES. SEC. G2413.2.
  
 11. PLEASE SUBMIT MANUFACTURER?S SPECIFICATION
 SHEETS/INSTALLATION MANUAL FOR HEATER EQUIPMENT TO
 VERIFY COMPLIANCE WITH 2020 FBC RES. SEC. G2408.1.
  
 12. PLEASE SUBMIT THE SIZING TABLE USED IN THE DESIGN
 FOR THE GAS SYSTEM OR PLACE A NOTE ON PLANS LISTING THE
 SIZING TABLES FROM GAS CODES OR ANOTHER STANDARD USED
 IN THIS SYSTEM'S DESIGN PER THE 2020 FBC RES. SEC.
 G2413.3.
  
 13. PLEASE SHOW ALL UNIONS IN FRONT OF THE REGULATOR
 ONE INCH OF EITHER SIDE PER THE 2020 FBC RES. SEC
 G2421.2.
  
 14. A REGULATOR IS REQUIRED TO BRING THE SYSTEM DOWN TO
 10.5 INCH WC. PLEASE SUBMIT THE MANUFACTURER?S
 SPECIFICATIONS FOR THE PRESSURE REGULATORS PER THE 2020
 FBC RES. SEC. G2421.1.
  
 15. SHOW DRIP LEG ON EQUIPMENT INSTALLED PER THE 2020
 FBC RES. SEC. G2419.2.
  
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND, WILL HELP EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  