2021-06-16 17:04:25ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 1) SEPARATE PERMIT/PLANS REQUIRED FOR GENERATOR.
  
 2) RISER DIAGRAM AND PANEL SCHEDULE DO NOT MATCH 1/0,
 2/0...
  
 3) NO GROUNDING ELECTRODE SYSTEM SHOWN AT GUEST
 QUARTERS, 250.32
  
 4) NO SMOKE ALARMS SHOWN. FBC R314/315
  
 5) ELECTRIC LIGHT PLAN SHOWS TWO FIRST FLOORS AND TWO
 SECOND FLOORS?
  
 6) GUEST QUARTERS TO HAVE A MAIN BREAKER IN PANEL PER
 225.31,