| Plan Review Notes For Permit 21060240 |
| Permit Number |
21060240 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2021-06-16 17:04:25 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | FLORIDA BUILDING CODE 2020 7TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED | | | NFPA 70 2017 EDITION | | | | | | JAKE LEAHY BN, BU, PX | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | 1) SEPARATE PERMIT/PLANS REQUIRED FOR GENERATOR. | | | | | | 2) RISER DIAGRAM AND PANEL SCHEDULE DO NOT MATCH 1/0, | | | 2/0... | | | | | | 3) NO GROUNDING ELECTRODE SYSTEM SHOWN AT GUEST | | | QUARTERS, 250.32 | | | | | | 4) NO SMOKE ALARMS SHOWN. FBC R314/315 | | | | | | 5) ELECTRIC LIGHT PLAN SHOWS TWO FIRST FLOORS AND TWO | | | SECOND FLOORS? | | | | | | 6) GUEST QUARTERS TO HAVE A MAIN BREAKER IN PANEL PER | | | 225.31, |
|