Plan Review Notes
Plan Review Notes For Permit 21060232
Permit Number 21060232
Review Stop B
Sequence Number 1
Notes
Date Text
2021-07-01 17:22:50WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 21060232
 ADD: 1200 S. FLAGLER DR. # 1405
 CONT: ESP CONSTRUCTION, INC.
 TEL: 561-718-5313
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: THURS. JULY 01/2021
 ACTION: DENIED
  
 1) THE DESCRIPTION OF WORK TO BE COMPLETED ON THE
 PERMIT APPLICATION AND ON THE PLANS IS NOT CLEAR,
 INSTALL NEW TILE IN (2) BATHROOM BATHING AREAS ONLY. IS
 THIS WORK TO REPLACE TILE IN THE WALL SURROUND OF THE
 TUB? THE SECOND QUESTION IS THE FLOORING IN BOTH
 BATHROOMS TO BE REMOVED AND ASSUMED NEW FLOOR TILE TO
 BE INSTALLED? A BETTER DISCERPTION OF WORK WILL BE
 HELPFUL, THANK YOU. 107.2.1.2 ADDITIONAL INFORMATION IS
 REQUIRED.
  
 2) TUB TILE SURROUND. IS THE TUB/ SHOWER VALVE BEING
 REPLACED? 107.2.1.2. ADDITIONAL INFORMATION IS
 REQUIRED. IF BEING REPLACED THERE WILL BE COMMENTS FROM
 THE PLUMBING REVIEWER ABOUT THE VALVE.
  
 3A) TUB SURROUND TYPE OF BACKING ON THE WALLS. 2020
 FBC-B 2509.2 BASE FOR TILE. MATERIALS USED AS A BASE
 FOR WALL TILE IN TUB AND SHOWER AREAS AND WALLS AND
 CEILING PANELS IN SHOWER AREAS SHALL BE OF MATERIALS
 LISTED IN TABLE 2509.2 AND INSTALLED IN ACCORDANCE WITH
 MANUFACTURER?S RECOMMENDATIONS. WATER RESISTANT GYPSUM
 BACKING BOARD SHALL BE USED AS A BASE FOR TILE IN WATER
 CLOSET COMPARTMENT WALLS WHEN INSTALLED IN ACCORDANCE
 WITH GA-216 OR ASTM C840 AND THE MANUFACTURE?S
 RECOMMENDATIONS.
  
 3B) SHOW ON PLANS. 2020 FBC-B SHOWERS & TUBS 1210.3.
 SHOWER COMPARTMENTS AND BATHTUBS WITH INSTALLED SHOWER
 HEADS SHALL BE FINISHED WITH A NONABSORBENT SURFACE TO
 A HEIGHT NOT LESS THAN 72 INCHES ABOVE THE DRAIN INLET.
  
 4) FLOOR TILE AND UNDERLAYMENT REQUIREMENTS SPECIFY THE
 TYPE OF FLOOR UNDERLAYMENT.
 FLOOR INSULATION/ UNDERLAYMENT (FBC-B 2020) FOR TILE,
 STONE, MARBLE, VINYL AND WOOD FLOORING ALL NEED TO HAVE
 HAD THE SOUND UNDERLAYMENT TESTED FLOOR ASSEMBLIES TO
 THE FOLLOWING STANDARDS AND MEET THE QUALIFICATIONS
 LISTED UNDER EACH OF THE STANDARDS FOR A 6 INCH
 CONCRETE FLOOR ASSEMBLY/ NO DROPPED CEILING:
 PLEASE PROVIDE ALL THREE TEST REPORTS FOR TYPE I AND OR
 TYPE II BUILDINGS SHOWING COMPLIANCE WITH:
  
 4A) FBC-B 2020 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E-492.
  
 4B) FBC-B 2020 1207.2 AIR-BORNE SOUND. WALLS,
 PARTITIONS AND FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR
 AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E
 90.
  
 4C) FLAME SPREAD- FBC-B 2020 603.1. EXCEPTION 2.
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200.
  
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
  
 5) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
 PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID
 19
 IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS
 561-718-9724.
 WORKING HOURS ARE MON.- WED. 8:00 AM- NOON. PART-TIME/
 RETIRED.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  