2022-05-09 09:18:55ELECTRIC REVIEW FAILED
 1) PLEASE PROVIDE DETAILS FOR ATS, RATINGS, OVERCURRENT
 PROTECTION. 215.5
 2) PLEASE PROVIDE AN ELECTRIC RECEPTACLE FOR SECOND
 BASIN IN BATH #3. 210.52(D)
 3) PLEASE PROVIDE A NOTE STATING ELEVATOR, GENERATOR,
 POOL AND LOW VOLTAGE LIGHTING REQUIRE SEPERATE PERMITS.
 FBC 107.2
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  