| 2022-05-23 10:39:10 | NEW SINGE FAMILY RESIDENCE (R3), 4TH BUILDING REVIEW |
| | COMMENTS |
| | CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS. |
| | PERMIT #21060227. |
| | |
| | NOTE: |
| | BUILDING REVIEW MAY BE APPROVED WITH PROVISO. PROVISO |
| | MEANS CONTRACTOR WILL SUBMIT REQUIRED INFORMATION AFTER |
| | THE PERMIT IS ISSUED BUT BEFORE INSPECTIONS TO AVOID |
| | CONFLICTS/DELAYS. REVISION FEES MAY APPLY. CONTRACTOR |
| | TO ADVICE IF PROVISO OPTION IS PREFERRED AT THIS TIME |
| | OR IF RE-SUBMITTING REQUIRED INFORMATION BEFORE PERMIT |
| | ISSUANCE. |
| | |
| | |
| | 1- UNDER SEPARATE PERMIT. SEE ITEM #12 BELOW. |
| | 1(G)PROVIDE COMPLETE FRAMING DETAILS/SPECIFICATIONS FOR |
| | ELEVATOR SHAFT. DETAIL 4 ON SHEET A7 IS MISSING ALL |
| | STRUCTURAL FRAMING INFORMATION. SPECIFY ALL FRAMING |
| | MEMBERS AND CONNECTORS, INCLUDING THE BRACING TO |
| | SUPPORT THE ELEVATOR. |
| | SEC. R301.1 FBC-RESIDENTIAL. |
| | NOTE: SEE HOISTWAY PLAN #4 ON SHEET A7. |
| | |
| | ***PREVIOUS COMMENT. |
| | RESPONSE TO ARCHITECTURAL PLANS SUBMITTED: |
| | 2(A) DEFERRED SUBMITTAL: (NOTE: NEED TO PROVIDE |
| | INFORMATION FOR REVIEW BEFORE INSTALLATION/INSPECTION |
| | TO AVOID CONFLICTS/DELAYS): |
| | PROVIDE COMPLETE DETAILS/SPECIFICATIONS FOR BALCONIES |
| | CLAY TILE RAILING AS SHOWN ON PLANS. SPECIFY ALL |
| | FRAMING MEMBERS AND ALL CONNECTORS. SPECIFY CLAY TILE |
| | INSTALLATION. DETAIL 7 ON SHEET A7 IS MISSING ALL THIS |
| | INFORMATION. SEC. R301.1 FBC-RESIDENTIAL. |
| | |
| | 2(B)DEFERRED SUBMITTAL: (NOTE: NEED TO PROVIDE |
| | INFORMATION FOR REVIEW BEFORE INSTALLATION/INSPECTION |
| | TO AVOID CONFLICTS/DELAYS): |
| | PROVIDE COMPLETE DETAILS/SPECIFICATIONS FOR CANOPIES AS |
| | SHOWN ON PLANS. SPECIFY ALL FRAMING MEMBERS AND |
| | CONNECTORS. DETAIL 1 ON SHEET A7 IS MISSING THIS |
| | INFORMATION. SEC. R301.1 FBC-RESIDENTIAL. |
| | |
| | 2(C)DEFERRED SUBMITTAL: (NOTE: NEED TO PROVIDE |
| | INFORMATION FOR REVIEW BEFORE INSTALLATION/INSPECTION |
| | TO AVOID CONFLICTS/DELAYS): |
| | PROVIDE COMPLETE FRAMING DETAILS/SPECIFICATIONS FOR |
| | TRELLIS PERGOLA. SPECIFY ALL FRAMING MEMBERS AND |
| | CONNECTORS. ARBOR DETAIL 4 ON SHEET A5 IS MISSING THIS |
| | INFORMATION. SEC. R301.1 FBC-RESIDENTIAL. |
| | |
| | 3- OK. |
| | |
| | ORIGINAL COMMENT: |
| | 4- DESIGNER OF RECORD TO NEEDS TO DEPICT THE BUILDING |
| | THERMAL ENVELOPE AND SPECIFY INSULATION MATERIALS AND |
| | THEIR R-VALUES. |
| | SEC. R103.2 FBC-ENERGY CONSERVATION. |
| | |
| | RESPONSE: |
| | REPEAT COMMENT. THIS IS NOT A DEFERRED ITEM. DESIGNER |
| | OF RECORD TO SPECIFY THE R-VALUE FOR CEILING, WALLS, |
| | FLOOR/CEILING ASSEMBLY BETWEEN GARAGE AND GUEST SUITE |
| | ABOVE. |
| | NOTE: COORDINATE WITH ENERGY CALCULATIONS TO AVOID |
| | CONFLICTS/DELAYS. |
| | |
| | ORIGINAL COMMENT: |
| | 5-PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC. |
| | R101.5 FBC-ENERGY CONSERVATION. COORDINATE WITH PLANS |
| | TO AVOID CONFLICTS/DELAYS. |
| | NOTE: PLEASE MAKE SURE CALCULATIONS ARE SIGNED BY ALL |
| | THE REQUIRED PARTIES, INCLUDING THE OWNER OR AUTHORIZED |
| | AGENT TO AVOID CONFLICT/DELAYS. |
| | |
| | RESPONSE: |
| | ENERGY CALCULATIONS SUBMITTED MAIN HOUSE: |
| | A)PROVIDE COMPLETE INFORMATION ON TOP OF FORM, |
| | INCLUDING OWNER'S NAME, BUILDER'S NAME, PERMIT OFFICE |
| | AND JURISDICTION (THIS JURISDICTION IS 604700). SEC. |
| | R101.5.1.1.2 FBC- ENERGY CONSERVATION. |
| | |
| | RESPONSE: |
| | REPEAT COMMENT. NOT ADDRESSED. |
| | |
| | B)WINDOWS OVERHANG DEPTH AND SEPARATION ON PAGE 3 DON'T |
| | MATCH PLANS. SEE PLANS AND REVISE AS REQUIRED TO MATCH |
| | PLANS. SEC. R101.5.1.1.2 FBC- ENERGY CONSERVATION. |
| | |
| | RESPONSE: |
| | REPEAT COMMENT. NOT ADDRESSED. |
| | |
| | C)BUILDER TO COMPLETE THE ENERGY PERFORMANCE LEVEL |
| | (EPL) DISPLAY CARD FOR EACH BUILDING. SEC. R405.4.3 |
| | FBC-ENERGY CONSERVATION. |
| | |
| | RESPONSE: |
| | REPEAT COMMENT. NOT ADDRESSED. |
| | |
| | ORIGINAL COMMENT: |
| | 6- LOT DRAINAGE |
| | PROVIDE DRAINAGE PLAN SHOWING COMPLIANCE WITH THE |
| | FOLLOWING: |
| | R401.3 FBC-RESIDENTIAL. SEC. 107.2.5 CITY AMENDMENTS. |
| | SEC. 110.9 CITY AMENDMENTS. |
| | NOTE: DRAINAGE PLAN TO SHOW THE EXISTING AND PROPOSED |
| | GRADE ELEVATIONS SHOWING HOW KEEPING WATER AWAY FROM |
| | ADJACENT PROPERTIES. |
| | |
| | RESPONSE: |
| | DETAIL SECTIONS A-A, B-B AND C-C ON SITE ENGINEERING |
| | PLAN SUBMITTED SHOW WATER RUNNING TO THE NEIGHBOR'S |
| | PROPERTY. THE WATER NEEDS TO BE CONTAINED WITHIN THE |
| | LOT AND/OR DIVERTED TO AN APPROVED POINT OF COLLECTION |
| | OR TOWARDS THE STREET. ALSO, THE PROPOSED POOL DECK IS |
| | TOO CLOSE TO THE NEIGHBOR'S PROPERTY AND THERE IS NOT |
| | INFORMATION SHOWING HOW THE WATER WILL REMAIN WITHIN |
| | THIS LOT IN THIS AREA. REVISE AS REQUIRED. ALSO, |
| | MISSING SECTION FOR FRONT OF THE LOT. |
| | SEC. 110 CITY AMENDMENTS. |
| | |
| | ORIGINAL COMMENT: |
| | 7- PROVIDE SURVEY SHOWING PROPOSED BUILDINGS AND |
| | SETBACKS. |
| | SEC. 107.2.5 CITY AMENDMENTS. |
| | |
| | RESPONSE: |
| | REPEAT COMMENT. NOT ADDRESSED. |
| | |
| | DEFERRED SUBMITTAL: |
| | 8-PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC |
| | 61G20-3.001 FOR |
| | (NOTE: PROVIDE COMPLETE INFORMATION FOR REVIEW PRIOR TO |
| | INSTALLATION TO AVOID CONFLICTS/DELAYS. ALL PRODUCT |
| | APPROVALS NEED TO BE APPROVED IN WRITING BY DESIGNER OF |
| | RECORD PRIOR TO SUBMITTAL): |
| | A)ALL EXTERIOR DOORS. |
| | B)WINDOWS. |
| | C)WINDOW MULLIONS (NOTE: NEED TO SPECIFY MULLION SIZE |
| | TO AVOID DELAYS/CONFLICTS). |
| | D)HURRICANE SHUTTERS IF DOORS AND WINDOWS DON'T HAVE |
| | IMPACT GLAZING. AND, PROVIDE COMPLETE INSTALLATION |
| | SCHEDULE. SEE CITY SAMPLE. |
| | E)CLAY TILE ROOF (3:12 PITCH). |
| | F)CLAY TILE ADHESIVE (IF SPECIFIED ON PLANS) AND MARK |
| | PADDY SIZE. |
| | G)CLAY TILE FOR GUARDRAIL SYSTEM SHOWN ON ELEVATIONS. |
| | H)SPRAY FOAM INSULATION SPECIFIED ON |
| | PLANS.(NOTE:PROVIDE ICC EVALUATION REPORT). |
| | |
| | 9- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| | (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS |
| | REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS. |
| | |
| | 10- OK. |
| | |
| | 11- FUTURE CUSTOM GLASS WINE ROOM WILL BE ON A SEPARATE |
| | PERMIT. |
| | |
| | 12- FUTURE ELEVATOR WILL BE ON A SEPARATE PERMIT. |
| | |
| | WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE |
| | ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF |
| | THE REVISION MADE, IDENTIFYING THE SHEET OR |
| | SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL |
| | HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR |
| | ANTICIPATED COOPERATION. |
| | |
| | PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY |
| | QUESTIONS REGARDING THESE COMMENTS, |
| | JULIO GOMEZ |