Plan Review Notes
Plan Review Notes For Permit 21060227
Permit Number 21060227
Review Stop B
Sequence Number 4
Notes
Date Text
2022-05-23 10:39:10NEW SINGE FAMILY RESIDENCE (R3), 4TH BUILDING REVIEW
 COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 PERMIT #21060227.
  
 NOTE:
 BUILDING REVIEW MAY BE APPROVED WITH PROVISO. PROVISO
 MEANS CONTRACTOR WILL SUBMIT REQUIRED INFORMATION AFTER
 THE PERMIT IS ISSUED BUT BEFORE INSPECTIONS TO AVOID
 CONFLICTS/DELAYS. REVISION FEES MAY APPLY. CONTRACTOR
 TO ADVICE IF PROVISO OPTION IS PREFERRED AT THIS TIME
 OR IF RE-SUBMITTING REQUIRED INFORMATION BEFORE PERMIT
 ISSUANCE.
  
  
 1- UNDER SEPARATE PERMIT. SEE ITEM #12 BELOW.
 1(G)PROVIDE COMPLETE FRAMING DETAILS/SPECIFICATIONS FOR
 ELEVATOR SHAFT. DETAIL 4 ON SHEET A7 IS MISSING ALL
 STRUCTURAL FRAMING INFORMATION. SPECIFY ALL FRAMING
 MEMBERS AND CONNECTORS, INCLUDING THE BRACING TO
 SUPPORT THE ELEVATOR.
 SEC. R301.1 FBC-RESIDENTIAL.
 NOTE: SEE HOISTWAY PLAN #4 ON SHEET A7.
  
 ***PREVIOUS COMMENT.
 RESPONSE TO ARCHITECTURAL PLANS SUBMITTED:
 2(A) DEFERRED SUBMITTAL: (NOTE: NEED TO PROVIDE
 INFORMATION FOR REVIEW BEFORE INSTALLATION/INSPECTION
 TO AVOID CONFLICTS/DELAYS):
 PROVIDE COMPLETE DETAILS/SPECIFICATIONS FOR BALCONIES
 CLAY TILE RAILING AS SHOWN ON PLANS. SPECIFY ALL
 FRAMING MEMBERS AND ALL CONNECTORS. SPECIFY CLAY TILE
 INSTALLATION. DETAIL 7 ON SHEET A7 IS MISSING ALL THIS
 INFORMATION. SEC. R301.1 FBC-RESIDENTIAL.
  
 2(B)DEFERRED SUBMITTAL: (NOTE: NEED TO PROVIDE
 INFORMATION FOR REVIEW BEFORE INSTALLATION/INSPECTION
 TO AVOID CONFLICTS/DELAYS):
 PROVIDE COMPLETE DETAILS/SPECIFICATIONS FOR CANOPIES AS
 SHOWN ON PLANS. SPECIFY ALL FRAMING MEMBERS AND
 CONNECTORS. DETAIL 1 ON SHEET A7 IS MISSING THIS
 INFORMATION. SEC. R301.1 FBC-RESIDENTIAL.
  
 2(C)DEFERRED SUBMITTAL: (NOTE: NEED TO PROVIDE
 INFORMATION FOR REVIEW BEFORE INSTALLATION/INSPECTION
 TO AVOID CONFLICTS/DELAYS):
 PROVIDE COMPLETE FRAMING DETAILS/SPECIFICATIONS FOR
 TRELLIS PERGOLA. SPECIFY ALL FRAMING MEMBERS AND
 CONNECTORS. ARBOR DETAIL 4 ON SHEET A5 IS MISSING THIS
 INFORMATION. SEC. R301.1 FBC-RESIDENTIAL.
  
 3- OK.
  
 ORIGINAL COMMENT:
 4- DESIGNER OF RECORD TO NEEDS TO DEPICT THE BUILDING
 THERMAL ENVELOPE AND SPECIFY INSULATION MATERIALS AND
 THEIR R-VALUES.
 SEC. R103.2 FBC-ENERGY CONSERVATION.
  
 RESPONSE:
 REPEAT COMMENT. THIS IS NOT A DEFERRED ITEM. DESIGNER
 OF RECORD TO SPECIFY THE R-VALUE FOR CEILING, WALLS,
 FLOOR/CEILING ASSEMBLY BETWEEN GARAGE AND GUEST SUITE
 ABOVE.
 NOTE: COORDINATE WITH ENERGY CALCULATIONS TO AVOID
 CONFLICTS/DELAYS.
  
 ORIGINAL COMMENT:
 5-PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC.
 R101.5 FBC-ENERGY CONSERVATION. COORDINATE WITH PLANS
 TO AVOID CONFLICTS/DELAYS.
 NOTE: PLEASE MAKE SURE CALCULATIONS ARE SIGNED BY ALL
 THE REQUIRED PARTIES, INCLUDING THE OWNER OR AUTHORIZED
 AGENT TO AVOID CONFLICT/DELAYS.
  
 RESPONSE:
 ENERGY CALCULATIONS SUBMITTED MAIN HOUSE:
 A)PROVIDE COMPLETE INFORMATION ON TOP OF FORM,
 INCLUDING OWNER'S NAME, BUILDER'S NAME, PERMIT OFFICE
 AND JURISDICTION (THIS JURISDICTION IS 604700). SEC.
 R101.5.1.1.2 FBC- ENERGY CONSERVATION.
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED.
  
 B)WINDOWS OVERHANG DEPTH AND SEPARATION ON PAGE 3 DON'T
 MATCH PLANS. SEE PLANS AND REVISE AS REQUIRED TO MATCH
 PLANS. SEC. R101.5.1.1.2 FBC- ENERGY CONSERVATION.
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED.
  
 C)BUILDER TO COMPLETE THE ENERGY PERFORMANCE LEVEL
 (EPL) DISPLAY CARD FOR EACH BUILDING. SEC. R405.4.3
 FBC-ENERGY CONSERVATION.
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED.
  
 ORIGINAL COMMENT:
 6- LOT DRAINAGE
 PROVIDE DRAINAGE PLAN SHOWING COMPLIANCE WITH THE
 FOLLOWING:
 R401.3 FBC-RESIDENTIAL. SEC. 107.2.5 CITY AMENDMENTS.
 SEC. 110.9 CITY AMENDMENTS.
 NOTE: DRAINAGE PLAN TO SHOW THE EXISTING AND PROPOSED
 GRADE ELEVATIONS SHOWING HOW KEEPING WATER AWAY FROM
 ADJACENT PROPERTIES.
  
 RESPONSE:
 DETAIL SECTIONS A-A, B-B AND C-C ON SITE ENGINEERING
 PLAN SUBMITTED SHOW WATER RUNNING TO THE NEIGHBOR'S
 PROPERTY. THE WATER NEEDS TO BE CONTAINED WITHIN THE
 LOT AND/OR DIVERTED TO AN APPROVED POINT OF COLLECTION
 OR TOWARDS THE STREET. ALSO, THE PROPOSED POOL DECK IS
 TOO CLOSE TO THE NEIGHBOR'S PROPERTY AND THERE IS NOT
 INFORMATION SHOWING HOW THE WATER WILL REMAIN WITHIN
 THIS LOT IN THIS AREA. REVISE AS REQUIRED. ALSO,
 MISSING SECTION FOR FRONT OF THE LOT.
 SEC. 110 CITY AMENDMENTS.
  
 ORIGINAL COMMENT:
 7- PROVIDE SURVEY SHOWING PROPOSED BUILDINGS AND
 SETBACKS.
 SEC. 107.2.5 CITY AMENDMENTS.
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED.
  
 DEFERRED SUBMITTAL:
 8-PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC
 61G20-3.001 FOR
 (NOTE: PROVIDE COMPLETE INFORMATION FOR REVIEW PRIOR TO
 INSTALLATION TO AVOID CONFLICTS/DELAYS. ALL PRODUCT
 APPROVALS NEED TO BE APPROVED IN WRITING BY DESIGNER OF
 RECORD PRIOR TO SUBMITTAL):
 A)ALL EXTERIOR DOORS.
 B)WINDOWS.
 C)WINDOW MULLIONS (NOTE: NEED TO SPECIFY MULLION SIZE
 TO AVOID DELAYS/CONFLICTS).
 D)HURRICANE SHUTTERS IF DOORS AND WINDOWS DON'T HAVE
 IMPACT GLAZING. AND, PROVIDE COMPLETE INSTALLATION
 SCHEDULE. SEE CITY SAMPLE.
 E)CLAY TILE ROOF (3:12 PITCH).
 F)CLAY TILE ADHESIVE (IF SPECIFIED ON PLANS) AND MARK
 PADDY SIZE.
 G)CLAY TILE FOR GUARDRAIL SYSTEM SHOWN ON ELEVATIONS.
 H)SPRAY FOAM INSULATION SPECIFIED ON
 PLANS.(NOTE:PROVIDE ICC EVALUATION REPORT).
  
 9- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 10- OK.
  
 11- FUTURE CUSTOM GLASS WINE ROOM WILL BE ON A SEPARATE
 PERMIT.
  
 12- FUTURE ELEVATOR WILL BE ON A SEPARATE PERMIT.
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,