Plan Review Notes
Plan Review Notes For Permit 21060227
Permit Number 21060227
Review Stop SIGNATURE
Sequence Number 3
Notes
Date Text
2022-04-06 17:40:27THIRD SIGNATURE REVIEW:
  
 1- DRAWINGS DON'T HAVE ORIGINAL DIGITAL SEAL/SIGNATURE
 BY THE ARCHITECT AND ENGINEER OF RECORD. ALL DRAWINGS
 NEED TO HAVE ORIGINAL DIGITAL L SEAL/SIGNATURE AS
 REQUIRED BY CHAPTER 481 F.S. AND CHAPTER 471 F.S. WHEN
 SUBMITTING FOR PUBLIC RECORDS.
  
 NOTE: SUBMIT DRAWINGS ELECTRONICALLY WITH
 ARCHITECT'S/ENGINEER'S DIGITAL SIGNATURE OR PROVIDE
 HARD COPY PLANS WITH ARCHITECT'S ORIGINAL SEAL AND
 SIGNATURE.
  
 2- ENERGY CALCULATIONS AND EQUIPMENT SIZING
 CALCULATIONS DON'T HAVE ENGINEER'S ORIGINAL DIGITAL
 SEAL/SIGNATURE. NEED TO HAVE ORIGINAL DIGITAL L
 SEAL/SIGNATURE AS REQUIRED BY CHAPTER 471 F.S. WHEN
 SUBMITTING DRAWINGS/DOCUMENTS FOR PUBLIC RECORDS.
  
  
 ENGINEERS
 61G15-23.004 PROCEDURES FOR DIGITALLY SIGNING AND
 SEALING ELECTRONICALLY TRANSMITTED PLANS,
 SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS.
  
 ARCHITECTS
 61G1-16.005 PROCEDURES FOR DIGITALLY SIGNING AND
 SEALING AND FOR ELECTRONICALLY TRANSMITTING PLANS,
 SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS.
  
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
  