| Plan Review Notes For Permit 21060227 |
| Permit Number |
21060227 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2022-01-29 12:34:04 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | FLORIDA BUILDING CODE 2020 7TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED | | | NFPA 70 2017 EDITION | | | | | | JAKE LEAHY BN, BU, PX | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | 1) NO RISER DIAGRAM SHOWN 215.5 | | | | | | 2) NO LOAD CALCULATION SUBMITTED. 215.5 | | | | | | 3) MASTRE BATH HAS PENDANT FIXTURE OVER TUB, NOT | | | ALLOWED 410.10(D) | | | | | | (D) BATHTUB AND SHOWER AREAS. NO PARTS OF | | | CORD-CONNECTED LUMINAIRES, CHAIN-, CABLE-, OR | | | CORD-SUSPENDED LUMINAIRES, LIGHTING TRACK, PENDANTS, OR | | | CEILING-SUSPENDED (PADDLE) FANS SHALL BE LOCATED WITHIN | | | A ZONE MEASURED 900 MM (3 FT) HORIZONTALLY AND 2.5 M (8 | | | FT) VERTICALLY FROM THE TOP OF THE BATHTUB RIM OR | | | SHOWER STALL THRESHOLD. THIS ZONE IS ALL ENCOMPASSING | | | AND INCLUDES THE SPACE DIRECTLY OVER THE TUB OR SHOWER | | | STALL. LUMINAIRES LOCATED WITHIN THE ACTUAL OUTSIDE | | | DIMENSION OF THE BATHTUB OR SHOWER TO A HEIGHT OF 2.5 M | | | (8 FT) VERTICALLY FROM THE TOP OF THE BATHTUB RIM OR | | | SHOWER THRESHOLD SHALL BE MARKED FOR DAMP LOCATIONS, OR | | | MARKED FOR WET LOCATIONS WHERE SUBJECT TO SHOWER SPRAY. | | | | | | 4) PANEL SCHEDULE(S) REQUIRED TO VERUFY LOADS IN LOAD | | | CALCLUATION 215.5 | | | |
|