2022-01-29 12:34:04ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 1) NO RISER DIAGRAM SHOWN 215.5
  
 2) NO LOAD CALCULATION SUBMITTED. 215.5
  
 3) MASTRE BATH HAS PENDANT FIXTURE OVER TUB, NOT
 ALLOWED 410.10(D)
  
 (D) BATHTUB AND SHOWER AREAS. NO PARTS OF
 CORD-CONNECTED LUMINAIRES, CHAIN-, CABLE-, OR
 CORD-SUSPENDED LUMINAIRES, LIGHTING TRACK, PENDANTS, OR
 CEILING-SUSPENDED (PADDLE) FANS SHALL BE LOCATED WITHIN
 A ZONE MEASURED 900 MM (3 FT) HORIZONTALLY AND 2.5 M (8
 FT) VERTICALLY FROM THE TOP OF THE BATHTUB RIM OR
 SHOWER STALL THRESHOLD. THIS ZONE IS ALL ENCOMPASSING
 AND INCLUDES THE SPACE DIRECTLY OVER THE TUB OR SHOWER
 STALL. LUMINAIRES LOCATED WITHIN THE ACTUAL OUTSIDE
 DIMENSION OF THE BATHTUB OR SHOWER TO A HEIGHT OF 2.5 M
 (8 FT) VERTICALLY FROM THE TOP OF THE BATHTUB RIM OR
 SHOWER THRESHOLD SHALL BE MARKED FOR DAMP LOCATIONS, OR
 MARKED FOR WET LOCATIONS WHERE SUBJECT TO SHOWER SPRAY.
  
 4) PANEL SCHEDULE(S) REQUIRED TO VERUFY LOADS IN LOAD
 CALCLUATION 215.5
  