Plan Review Notes
Plan Review Notes For Permit 21060227
Permit Number 21060227
Review Stop B
Sequence Number 2
Notes
Date Text
2022-02-16 17:22:21NEW SINGE FAMILY RESIDENCE (R3), SECOND BUILDING REVIEW
 COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 PERMIT #21060227.
  
 ORIGINAL COMMENT:
 1- STRUCTURAL DRAWINGS WERE NOT SUBMITTED. NEED TO
 PROVIDE COMPLETE SET OF STRUCTURAL DRAWINGS. UNABLE TO
 DO THE REVIEW. SEC. 107.2.1 CITY AMENDMENTS.
 SPECIFY THE CURRENT CODE IN EFFECT. BUILDING EXPOSURE
 (NOTE: THIS BUILDING IS LOCATED IN EXPOSURE "D".
 ULTIMATE AND NOMINAL WIND SPEEDS. ALL LIVE AND DEAD
 LOADS (INCLUDING ATTIC LIVE LOADS). ALL COMPONENTS AND
 CLADDING DESIGN PRESSURES. SEC. R301.2.1 FBC
 RESIDENTIAL.
  
 RESPONSE TO STRUCTURAL PLANS SUBMITTED:
 1(A)THERE IS A CONCERN ABOUT THE SUPPORT OF THE SECOND
 FLOOR GIRDER TRUSS RUNNING FROM THE STAIRWAY TO THE
 WALL BETWEEN THE FUTURE BUTLER'S PANTRY AND FUTURE WINE
 ROOM. FOUNDATION PLAN ON SHEET S1 SPECIFIES WD1 COLUMN
 ON ONE END AND FIRST FLOOR LIFT BEAM PLAN ON SHEET S2
 SPECIFIES DOUBLE 2X6 STUD ON THE OTHER END. PROVIDE
 CALCULATIONS SHOWING THAT THE PROPOSED WOOD COLUMNS
 (10' HIGH) ARE ADEQUATE TO SUPPORT ALL THE SECOND FLOOR
 LOADS. SEC. R301.1 FBC-RESIDENTIAL, SEC. 107.2.1.2 CITY
 AMENDMENTS.
  
 1(B)CLARIFY WHY FOOTER FOR GIRDER TRUSS MENTIONED ABOVE
 WAS ENLARGED AT THE DOUBLE 2X6 COLUMN, BUT IT WAS NOT
 ENLARGED AT THE WD1 COLUMN?. SEC. 107.2.1.2 CITY
 AMENDMENTS.
  
 1(C)FIRST FLOOR LIFT BEAM PLAN ON SHEET S2 SHOWS THAT
 GIRDER TRUSS MENTIONED ABOVE IS NOT RESTING ON TOP OF
 WD1 COLUMN. THE SUPPORT IS OFFSET. PROVIDE
 DETAIL/SPECIFICATIONS FOR THIS TRUSS TO POST
 CONNECTION. SEC. 107.2.1.2 CITY AMENDMENTS.
  
 1(D)BASED ON TABLE R301.2(2) FBC-RESIDENTIAL, THE
 COMPONENTS AND CLADDING WIND LOADS SPECIFIED ON SHEETS
 A-3 AND A-4 ARE TOO LOW. REVISE AS REQUIRED OR PROVIDE
 ACTUAL CALCULATIONS. SEC. 107.2.1.2 CITY AMENDMENTS.
  
 1(E)PROVIDE COMPLETE DETAILS/SPECIFICATIONS FOR TOP AND
 BOTTOM CONNECTIONS OF 8X8 AND 12X12 WOOD COLUMNS SHOWN
 ON THE SECOND FLOOR BALCONIES. SEC. R301.1
 FBC-RESIDENTIAL.
 NOTE: 12X12 COLUMNS ARE RESTING ON CONCRETE. 8X8
 COLUMNS ARE RESTING ON CANTILEVER WOOD BALCONY DECK.
  
 1(F)PROVIDE COMPLETE FRAMING DETAILS FOR SECOND FLOOR
 FRENCH DOORS BY THE MASTER SUITE BALCONY. SPECIFY ALL
 FRAMING MEMBERS AND CONNECTORS. SEC. R301.1
 FBC-RESIDENTIAL, SEC. 107.2.1.2 CITY AMENDMENTS.
  
 1(G)PROVIDE COMPLETE FRAMING DETAILS/SPECIFICATIONS FOR
 ELEVATOR SHAFT. DETAIL 4 ON SHEET A7 IS MISSING ALL
 STRUCTURAL FRAMING INFORMATION. SPECIFY ALL FRAMING
 MEMBERS AND CONNECTORS, INCLUDING THE BRACING TO
 SUPPORT THE ELEVATOR.
 SEC. R301.1 FBC-RESIDENTIAL.
 NOTE: SEE HOISTWAY PLAN #4 ON SHEET A7.
  
 ORIGINAL COMMENT:
 2- ARCHITECTURAL PLANS ARE INCOMPLETE. SEC. 107.2.1
 CITY AMENDMENTS.
 NEED THE FOLLOWING: TO SHOW THE DIMENSIONS OF ALL ROOMS
 AND AREAS; DOORS AND WINDOWS SCHEDULES; BEDROOMS
 EMERGENCY EGRESS, SECOND FLOOR WINDOW FALL PROTECTION
 (IF REQUIRED); COMPLETE CONSTRUCTION DETAILS AND
 SPECIFICATIONS FOR ALL STAIRWAYS, HANDRAILS AND
 GUARDRAILS; COMPLETE DETAILS AND SPECIFICATIONS FOR
 FIREPLACE; COMPLETE DETAILS AND SPECIFICATIONS FOR POOL
 TRELLIS CONSTRUCTION; COMPLETE DETAILS AND
 SPECIFICATIONS FOR ROOF VENTILATION; COMPLETE DETAILS
 AND SPECIFICATIONS FOR ROOF CLAY TILE INSTALLATION AND
 ROOFING UNDERLAYMENT; SPECIFY FASTENING; FIRE RATED
 CONSTRUCTION ABOVE GARAGE; COMPLETE DETAILS AND
 SPECIFICATIONS FOR FIREBLOCKING AND DRAFSTOPPING;
 COMPLETE DETAILS AND SPECIFICATIONS FOR CANOPY AND
 AWNING CONSTRUCTION SHOWN ON PLANS; COMPLETE DETAILS
 AND SPECIFICATIONS FOR CARPORT CONSTRUCTION SHOWN ON
 PLANS; ATTIC ACCESS SIZE; COMPLETE EQUIPMENT ALUMINUM
 SCREENINGS DETAILS AND SPECIFICATIONS; COMPLETE DETAILS
 AND SPECIFICATIONS FOR CLAY TILE GUARDRAIL SYSTEM SHOWN
 ON EXTERIOR ELEVATIONS; GARAGE STRUCTURAL BUCK DETAIL;
 DOORS AND WINDOWS STRUCTURAL BUCK DETAILS; COMPLETE
 DETAILS AND SPECIFICATIONS FOR ELEVATOR SHAFT
 CONSTRUCTION AND FOR ELEVATOR TO BE INSTALLED; CARBON
 MONOXIDE ALARMS, ETC.
  
 RESPONSE TO ARCHITECTURAL PLANS SUBMITTED:
 2(A)PROVIDE COMPLETE DETAILS/SPECIFICATIONS FOR
 BALCONIES CLAY TILE RAILING AS SHOWN ON PLANS. SPECIFY
 ALL FRAMING MEMBERS AND ALL CONNECTORS. SPECIFY CLAY
 TILE INSTALLATION. DETAIL 7 ON SHEET A7 IS MISSING ALL
 THIS INFORMATION. SEC. R301.1 FBC-RESIDENTIAL.
 NOTE: THIS COULD BE A DEFERRED SUBMITTAL.
  
 2(B)PROVIDE COMPLETE DETAILS/SPECIFICATIONS FOR
 CANOPIES AS SHOWN ON PLANS. SPECIFY ALL FRAMING MEMBERS
 AND CONNECTORS. DETAIL 1 ON SHEET A7 IS MISSING THIS
 INFORMATION. SEC. R301.1 FBC-RESIDENTIAL.
 NOTE: THIS COULD BE A DEFERRED SUBMITTAL.
  
 2(C)PROVIDE COMPLETE FRAMING DETAILS/SPECIFICATIONS FOR
 TRELLIS PERGOLA. SPECIFY ALL FRAMING MEMBERS AND
 CONNECTORS. ARBOR DETAIL 4 ON SHEET A5 IS MISSING THIS
 INFORMATION. SEC. R301.1 FBC-RESIDENTIAL.
 NOTE: THIS COULD BE A DEFERRED SUBMITTAL.
  
 2(D) DOORS AND WINDOWS STRUCTURAL BUCK INFORMATION
 SHOWN ON SHEET D1 AND DOORS AND WINDOWS STRUCTURAL BUCK
 INFORMATION SHOWN ON SHEET S11 DON'T MATCH. REVISE AS
 REQUIRED TO MATCH TO AVOID CONFLICTS/DELAYS. SEC.
 107.21 CITY AMENDMENTS.
  
 3- OK.
  
 ORIGINAL COMMENT:
 4- DESIGNER OF RECORD TO NEEDS TO DEPICT THE BUILDING
 THERMAL ENVELOPE AND SPECIFY INSULATION MATERIALS AND
 THEIR R-VALUES.
 SEC. R103.2 FBC-ENERGY CONSERVATION.
  
 RESPONSE:
 DESIGNER OF RECORD TO SPECIFY THE R-VALUE FOR CEILING,
 WALLS, FLOOR/CEILING ASSEMBLY BETWEEN GARAGE AND GUEST
 SUITE ABOVE.
  
 ORIGINAL COMMENT:
 5-PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC.
 R101.5 FBC-ENERGY CONSERVATION. COORDINATE WITH PLANS
 TO AVOID CONFLICTS/DELAYS.
 NOTE: PLEASE MAKE SURE CALCULATIONS ARE SIGNED BY ALL
 THE REQUIRED PARTIES, INCLUDING THE OWNER OR AUTHORIZED
 AGENT TO AVOID CONFLICT/DELAYS.
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED.
  
 ORIGINAL COMMENT:
 6- LOT DRAINAGE
 PROVIDE DRAINAGE PLAN SHOWING COMPLIANCE WITH THE
 FOLLOWING:
 R401.3 FBC-RESIDENTIAL.
 SEC. 107.2.5 CITY AMENDMENTS.
 SEC. 110.9 CITY AMENDMENTS.
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED.
 NOTE: DRAINAGE PLAN TO SHOW THE EXISTING AND PROPOSED
 GRADE ELEVATIONS SHOWING HOW KEEPING WATER AWAY FROM
 ADJACENT PROPERTIES.
  
 ORIGINAL COMMENT:
 7- PROVIDE SURVEY SHOWING PROPOSED BUILDINGS AND
 SETBACKS.
 SEC. 107.2.5 CITY AMENDMENTS.
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED.
  
 ORIGINAL COMMENT:
 8-PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC
 61G20-3.001 FOR
 (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED
 SUBMITTAL. PROVIDE COMPLETE INFORMATION FOR REVIEW
 PRIOR TO INSTALLATION TO AVOID CONFLICTS/DELAYS. ALL
 PRODUCT APPROVALS NEED TO BE APPROVED IN WRITING BY
 DESIGNER OF RECORD PRIOR TO SUBMITTAL):
  
 A)ALL EXTERIOR DOORS.
 B)WINDOWS.
 C)WINDOW MULLIONS (NOTE: NEED TO SPECIFY MULLION SIZE
 TO AVOID DELAYS/CONFLICTS).
 D)HURRICANE SHUTTERS IF DOORS AND WINDOWS DON'T HAVE
 IMPACT GLAZING. AND, PROVIDE COMPLETE INSTALLATION
 SCHEDULE. SEE CITY SAMPLE.
 E)CLAY TILE ROOF (3:12 PITCH).
 F)CLAY TILE ADHESIVE (IF SPECIFIED ON PLANS) AND MARK
 PADDY SIZE.
 G)CLAY TILE FOR GUARDRAIL SYSTEM SHOWN ON ELEVATIONS.
  
 RESPONSE:
 NOT ADDRESSED. PLEASE ADVICE IF SUBMITTING LATER AS A
 SUBMITTAL.
  
 9- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 ORIGINAL COMMENT:
 10- SEPARATE PERMIT APPLICATION FOR EACH BUILDING.
 PLEASE SUBMIT A SEPARATE PERMIT APPLICATION (AND
 SUB-PERMIT APPLICATIONS) FOR THE SEPARATE GARAGE/GUEST
 SUITE BUILDING. SAME PLANS CAN BE USED. SEPARATE PERMIT
 APPLICATIONS HELP TO COORDINATE INSPECTIONS FOR EACH
 BUILDING AND TO FACILITATE RECORDS KEEPING. SEC.
 107.2.1.3 CITY AMENDMENTS.
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED.
  
 11- FUTURE CUSTOM GLASS WINE ROOM WILL BE ON A SEPARATE
 PERMIT.
  
 12- FUTURE ELEVATOR WILL BE ON A SEPARATE PERMIT.
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  