| 2022-04-26 12:15:09 | 1ST REVIEW FBC-2020 RES. GAS |
| | PERMIT- 22031166 |
| | 4/26/2022 |
| | |
| | CODES IN EFFECT: |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION |
| | 2020 |
| | FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| | 2020 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. PLEASE NOTE THAT GAS CAN |
| | BE UNDER SEPARATE PERMIT IF REQUESTED BY THE GENERAL |
| | CONTRACTOR OF RECORD. |
| | |
| | 1) SHEET P401: PLEASE NOTE THAT SEPARATE PERMITS ARE |
| | REQUIRED FOR INSTALLATION OF THE GENERATOR AND POOL |
| | HEATER HOWEVER THE GENERATOR, AS SHOWN ON THE PLAN, |
| | SHALL BE RELOCATED TO BE A MINIMUM OF 10-FT AWAY FROM |
| | THE GARAGE WINDOW OPENING. PLEASE CORRECT THE PLANS AND |
| | THE RISER DRAWING- SEC. R305.5.1 FBC RES. |
| | |
| | 2) P401: REFER TO SEC. G2411.1- G2411.3 FBC RES AND, |
| | PROVIDE A NOTE OR DETAIL INDICATING HOW THE CSST PIPE |
| | WILL BE ELECTRICALLY CONTINUOUS AND BONDED TO AN |
| | EFFECTIVE GROUND FAULT CURRENT PATH. PLEASE SUBMIT |
| | MANUFACTURER?S SPECIFICATIONS FOR THE PIPING- SEC. |
| | G2414.5.4 FBC RES. |
| | |
| | 3) P401: PLACE A NOTE OR PROVIDE A DETAIL THAT THE |
| | GAS-FIRED TANKLESS WATER HEATER WILL BE ELEVATED A |
| | MINIMUM OF 18-INCHES ABOVE THE GARAGE FLOOR, OR A |
| | MINIMUM OF 6FT. IF NOT PROTECTED FROM VEHICLE IMPACT- |
| | SECS. G2408.2 & G2408.3 FBC RES. |
| | |
| | 4) P401: PROVIDE COMBUSTION AIR PLANS AND CALCULATIONS |
| | FOR THE WATER HEATER, RANGE, AND DRYERS- SEC. G2407.1 |
| | FBC RES. INDICATE HOW MAKEUP AIR WILL BE PROVIDED FOR |
| | THE DRYERS- SEC. G2439.5 FBC RES. |
| | |
| | 5) P401: PROVIDE A VENTING DIAGRAM FOR THE WATER |
| | HEATER- SEC. G2427.1 & G2448.1 FBC RES. SHOW THE TYPE |
| | AND SIZE OF VENT DUCT, TOTAL DUCT RUN, AND TERMINATION |
| | LOCATION WITH REQUIRED CAP AND CLEARANCE DISTANCE |
| | MEASUREMENTS- G2427.8 FBC RES. |
| | |
| | 6) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE DRYERS, |
| | RANGE, AND WATER HEATER- SEC. G2439.1, G2447.1, & |
| | G2448.1 FBC RES. |
| | |
| | 7) SUBMIT A GAS SUB-PERMIT APPLICATION- SEC.105.1 WPB. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |