| Plan Review Notes For Permit 21060214 |
| Permit Number |
21060214 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2021-06-04 10:53:23 | 1ST REVIEW FBC-2020 PLUMBING | | | PERMIT- 21060214 | | | 6/4/2021 | | | | | | CODES IN EFFECT: | | | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 | | | FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017 | | | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 | | | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 | | | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION | | | 2017 | | | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 | | | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION | | | 2017 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) SHEET P1.0: THE CONDENSATE FROM THE REFRIGERATION | | | SYSTEMS SHALL NOT DRAIN INTO THE SANITARY SYSTEM IN | | | ACCORDANCE WITH SEC. 90-126 CITY OF WEST PALM BEACH | | | CODE OF ORDINANCES. PLEASE PROVIDE AN APPROVED PLACE OF | | | DISPOSAL SUCH AS THE STORM DRAIN OR A DRYWELL- SECTION | | | 314.2.1 FBC P. THIS ISSUE WAS ALSO ADDRESSED UNDER | | | REVISION 21050388. PLEASE CORRECT THE PLANS. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL/PLUMBING PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|