Plan Review Notes
Plan Review Notes For Permit 21060214
Permit Number 21060214
Review Stop M
Sequence Number 1
Notes
Date Text
2021-06-03 13:14:541ST REVIEW FBC-2020 MECHANICAL
 PERMIT-21060214
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE PROVIDE THE REQUIRED INFORMATION FROM FBC M
 1102.1 (1-6)
 1102.1 GENERAL. THE SYSTEM CLASSIFICATION, ALLOWABLE
 REFRIGERANTS, MAXIMUM QUANTITY, ENCLOSURE REQUIREMENTS,
 LOCATION LIMITATIONS, AND FIELD PRESSURE TEST
 REQUIREMENTS SHALL BE DETERMINED AS FOLLOWS:
 1. DETERMINE THE REFRIGERATION SYSTEM'S CLASSIFICATION,
 IN ACCORDANCE WITH SECTION 1103.3.
 2. DETERMINE THE REFRIGERANT CLASSIFICATION IN
 ACCORDANCE WITH SECTION 1103.1.
 3. DETERMINE THE MAXIMUM ALLOWABLE QUANTITY OF
 REFRIGERANT IN ACCORDANCE WITH SECTION 1104, BASED ON
 TYPE OF
 REFRIGERANT, SYSTEM CLASSIFICATION AND OCCUPANCY.
 4. DETERMINE THE SYSTEM ENCLOSURE REQUIREMENTS IN
 ACCORDANCE WITH SECTION 1104.
 5. REFRIGERATION EQUIPMENT AND APPLIANCE LOCATION AND
 INSTALLATION SHALL BE SUBJECT TO THE LIMITATIONS OF
 CHAPTER 3.
 6. NON FACTORY-TESTED, FIELD-ERECTED EQUIPMENT AND
 APPLIANCES SHALL BE PRESSURE TESTED IN ACCORDANCE WITH
 SECTION
 1108.
 2) PLEASE PROVIDE THE CERTIFICATE OF TEST FOR ALL
 SYSTEMS CONTAINING 55 POUNDS OR MORE OF REFRIGERANT TO
 THE INSPECTOR. FBC M 1108.4
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  