| 2021-07-13 09:00:31 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2020 |
| | 7TH ED, CHAPTER 1. |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 |
| | 7TH EDITION |
| | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2020 |
| | 7TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION |
| | NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | FAC = FLORIDA ADMINISTRATIVE CODE |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1.MINI SPLIT NOT ON ELECTRICAL PLAN |
| | 2.PROVIDE SMOKE/CO ALARMS IN EACH LOCATION REQUIRED PER |
| | CODE. FBC RE R314.3, R315.1; WPB FBC 107.2.1 |
| | 3.PROVIDE WIRE AND BREAKER SIZE AND DISCONECT LOCATION |
| | 4.A BUILDING OR OTHER STRUCTURE THAT IS SERVED BY A |
| | BRANCH CIRCUIT OR FEEDER ON THE LOAD SIDE OF A SERVICE |
| | DISCONNECTING MEANS SHALL BE SUPPLIED BY ONLY ONE |
| | FEEDER OR BRANCH CIRCUIT. NEC 225.30 |
| | 5.A GROUNDING ELECTRODE SYSTEM IS REQUIRED TO BE |
| | ESTABLISHED AT EACH SEPARATE BUILDING OR STRUCTURE AND |
| | CONNECTED TOGETHER. PROVIDE DETAILS ON PLAN OF |
| | GROUNDING ELECTRODE SYSTEM AND WIRING. NEC 250.32; FBC |
| | RE E3607.3 |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. |
| | |