| Date |
Text |
| 2021-06-09 21:14:12 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. IS THIS STRUCTURE A DETACHED GARAGE? IF SO DOES THE |
| | STRUCTURE ALREADY HAVE ELECTRIC RAN TO IT? FBC 107.2.1 |
| | |
| | 2. PROVIDE RISER DIAGRAM OF EXISTING RESIDENTIAL |
| | SERVICE. NEC 220.16A1&2, 220.12, 220.14 |
| | FBC RE 3602.1, FBC RE 3602.2, FBC 107.2.1 |
| | |
| | 3. IS THIS TWO BEDROOMS OR ONE. ON PLAN TWO BEDROOMS |
| | ARE SHOWN AND NO RECEPTACLES OR LIGHTING IS SHOWN IN |
| | BEDROOM WEST OF BATHROOM. MISLABELED PERHAPS IT IS A |
| | CLOSET? FBC 107.2.1 |
| | |
| | 4. PROVIDE LOAD CALCULATION TO INCLUDE NEW AND EXISTING |
| | LOADS. NEC 220 |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | CODES IN EFFECT: |
| | |
| | HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B |
| | UILDING-PERMIT-FORMS |
| | |
| | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE 2020 7TH ED. |
| | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020 |
| | 7TH EDITION |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 |
| | 7TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION |
| | NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | V/R, |
| | |
| | FRANK GIAQUINTO III |
| | ELECTRICAL INSPECTOR |
| | ELECTRICAL PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | [email protected] |
| | CELL: 561-805-6744 |
| | |