2021-06-09 21:14:12ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. IS THIS STRUCTURE A DETACHED GARAGE? IF SO DOES THE
 STRUCTURE ALREADY HAVE ELECTRIC RAN TO IT? FBC 107.2.1
  
 2. PROVIDE RISER DIAGRAM OF EXISTING RESIDENTIAL
 SERVICE. NEC 220.16A1&2, 220.12, 220.14
 FBC RE 3602.1, FBC RE 3602.2, FBC 107.2.1
  
 3. IS THIS TWO BEDROOMS OR ONE. ON PLAN TWO BEDROOMS
 ARE SHOWN AND NO RECEPTACLES OR LIGHTING IS SHOWN IN
 BEDROOM WEST OF BATHROOM. MISLABELED PERHAPS IT IS A
 CLOSET? FBC 107.2.1
  
 4. PROVIDE LOAD CALCULATION TO INCLUDE NEW AND EXISTING
 LOADS. NEC 220
  
  
  
  
  
  
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B
 UILDING-PERMIT-FORMS
  
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO III
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 [email protected]
 CELL: 561-805-6744
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved