| 2021-07-02 15:27:19 | ****CORRECTIONS**** | | | | | | PETER E VALENTI | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6673 | | | | | | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | | | | BUILDING REVIEW DENIED: | | | | | | 1) FBC B 107.2.1, PLEASE PROVIDE, ON SHEET A-2, THE R | | | VALUE FOR WALL INSULATION. | | | 2) FBC EB 811.1, PLEASE PROVIDE ENERGY CALCULATIONS | | | COMPLETED ON REQUIRED FORM, SUCH AS FORM #405. | | | 3) FBC B 107.2.1, P-LEASE PROVIDE THE WINDOW/DOOR | | | PRODUCT APPROVALS. |
|