| 2021-08-05 16:31:47 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1 |
| | WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL |
| | MANUAL REVISED 2017 |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 |
| | 7TH EDITION |
| | FBC EX = FLORIDA EXISTING BUILDING CODE 2020 7TH |
| | EDITION |
| | FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION |
| | FAC= FLORIDA ADMINISTRATIVE CODE |
| | FS = FLORIDA STATUTES |
| | |
| | |
| | 2ND REVIEW |
| | PLUMBING COMMENTS: DENIED |
| | 1.THIS UNIT WAS BUILT UNDER THE FAIR HOUSING ACT OF |
| | MARCH 6, 1991, AND SHALL COMPLY WITH FAIR HOUSING ACT |
| | CHAPTER 7 |
| | A) SECOND REQUEST: PER WPB FBC 107.2.1, IDENTIFY THE |
| | COMPLIANT BATHROOM(S) AND IDENTIFY IT/THEM AS TYPE A |
| | AND/OR TYPE B (PLANS ARE NOT CLEAR IN THIS REGARD). |
| | PLEASE SHOW THE CLEAR FLOOR SPACES FOR THE FIXTURES. |
| | NOT SHOWN, PLEASE REFER TO THE FAIR HOUSING ACT DESIGN |
| | MANUAL CHAPTER 7 PART B FOR CLARIFICATION. |
| | B) SECOND REQUEST: PER WPB FBC 107.2.1, PLEASE SHOW THE |
| | CLEAR FLOOR SPACES FOR THE KITCHEN SINK AND APPLIANCES |
| | IN THE KITCHEN. NOT SHOWN, PLEASE REFER TO THE FAIR |
| | HOUSING ACT DESIGN MANUAL CHAPTER 7 PART A FOR |
| | CLARIFICATION. |
| | C) COMPLIED |
| | |
| | 2.SECOND REQUEST: FBC 2020 R307.2 IS NOT THE PREVAILING |
| | CODE. NOTE PERTAINING TO SHOWER/BATHTUB COMPARTMENT |
| | SHALL REFERENCE FBC PL 421.4.1: PLEASE NOTE THAT PER |
| | WPB FBC 101.2 AND 101.4.3 REQUIRES COMPLIANCE WITH THE |
| | FBC PL (FLORIDA PLUMBING CODE) UNLESS THE STRUCTURE IS |
| | A DETACHED ONE AND TWO FAMILY DWELLING AND MULTIPLE |
| | SINGLE FAMILY DWELLINGS (TOWNHOUSES0 NOT MORE THAN |
| | THREE STORIES ABOVE GRADE PLANE IN HEIGHT WITH A |
| | SEPARATE MEANS OF EGRESS AND THEIR ACCESSORY STRUCTURES |
| | SHALL COMPLY WITH THE FLORIDA BUILDING CODE, |
| | RESIDENTIAL. |
| | |
| | 3.COMPLIED |
| | |
| | 4.MASTER BATH: |
| | ?.A-1) IT WOULD APPEAR THAT THE LAVATORY IN EXISTING |
| | CONDITIONS IS AN INDIVIDUALLY VENTED FIXTURE DRAIN AND |
| | THE FLOOR PENETRATION WILL NOT BE RELOCATED. PER WPB |
| | FBC 107.2.1, CLARIFY/CONFIRM ON THE PLANS. IF THIS IS |
| | THE CASE PROVIDE NOTE ON PROPOSED FLOOR PLAN STATING |
| | "MODIFY EXISTING IN-WALL SANITARY WASTE AND VENT PIPING |
| | BY PROVIDING COMMON VENTING OF TWO (2) LAVATORIES; |
| | COMPLY WITH FBC PL SECTION 909.1, TABLE 909.1 AND |
| | SECTION 911." THIS IS IN LIEU OF REQUIRING A SANITARY |
| | RISER DIAGRAM FOR THIS CONDITION. IF THIS NOT THE |
| | CONDITION, A SANITARY RISER DIAGRAM WILL BE REQUIRED |
| | SHOWING HOW THIS PIPING WILL BE ACCOMPLISHED IN A |
| | MANNER THAT COMPLIES WITH THE REQUIREMENTS OF FBC PL |
| | CHAPTERS 7 AND 9. |
| | COMPLIED |
| | ?.A-2)SECOND REQUEST: ADDITIONALLY INDICATE TYPE OF |
| | MATERIAL (I.E. CAST IRON, PVC) OF DRAIN PIPE |
| | PENETRATING THROUGH THE FLOOR AND THE HORIZONTAL BRANCH |
| | BELOW. PROVIDE ASSEMBLY HAVING A FIRE-RESISTANCE RATING |
| | OF NOT LESS THAN 1 HOUR TO BE USED FOR DEALING WITH THE |
| | SHOWER FLOOR PENETRATION AS REQUIRED BY FBC 714.4.1 |
| | THROUGH 714.4.4.1.2 PER WPB FPC 107.2.1. SHOW HOW |
| | ABANDONED PENETRATION WILL BE REMEDIATED. |
| | ?.B) COMPLIED |
| | |
| | 5. COMPLIED |
| | |
| | 6.SECOND REQUEST: PROVIDE ASSEMBLY HAVING A |
| | FIRE-RESISTANCE RATING OF NOT LESS THAN 1 HOUR TO BE |
| | USED FOR DEALING WITH THE SHOWER FLOOR PENETRATION AS |
| | REQUIRED BY FBC 714.4.1 THROUGH 714.4.4.1.2 PER WPB FPC |
| | 107.2.1. SHOW HOW ABANDONED PENETRATION WILL BE |
| | REMEDIATED. |
| | |
| | 7. COMPLIED |
| | |
| | 8. COMPLIED |
| | |
| | 9. COMPLIED |
| | |
| | 10. NEW COMMENT: PER WPB FBC 107.2.1, RECONCILE A-1 |
| | WITH P-1. BATHTUBS ARE STILL SHOWN ON A-1 PROPOSED |
| | FLOOR PLAN. |
| | |
| | 11.NEW COMMENT: REGARDING NEW SHOWERS; |
| | -POST TENSION SLAB/ NEW HOLES. AS PREVIOUSLY NOTED BY |
| | THE BUILDING PLANS EXAMINER, THE PLAN IS SILENT AS IF |
| | THE LOCATION OF THE EXISTING TUB DRAIN IS GOING TO BE |
| | REUSED IN THE SAME LOCATION. IF NOT, THEN THE FLOOR |
| | SLAB WILL NEED TO BE X-RAYED TO FIND THE POST TENSION |
| | CHORD LOCATIONS. WPB FBC 107.2.1.2. ADDITIONAL |
| | INFORMATION IS REQUIRED. |
| | -THE PLAN INDICATES A RECTANGULAR TRENCH DRAIN WHICH |
| | WILL REQUIRE CUTTING OF THE ELEVATED STRUCTURAL SLAB TO |
| | INSTALL. PER WPB FBC 107.2.1, SPECIFY THE DRAIN TO BE |
| | INCORPORATED AND PROVIDE MANUFACTURER?S |
| | SPECIFICATION/INSTALLATION SHEETS. SAID DRAIN SHALL |
| | INCLUDE A MEMBRANE CLAMPING RING FOR USE WITH A SHOWER |
| | LINER. |
| | -IF CUTTING OF SLAB IS REQUIRED TO ACCOMMODATE SAID |
| | DRAIN IS REQUIRED, PROVIDE A DETAIL SHOWING THE DETAILS |
| | FOR CUTTING THE SLAB: SHOW THE DIMENSIONS OF THE |
| | OPENING, THE DIMENSIONS OF THE DRAIN, IMBED |
| | INFORMATION, THE MINIMUM THICKNESS OF THE CONCRETE TO |
| | BE REPLACED, AND THE PSI OF THE CONCRETE. SHOW THE SIZE |
| | AND LENGTH OF THE DOWELS, THE MINIMUM EMBEDMENT INTO |
| | THE EXISTING SLAB, THE ANCHORING MATERIAL FOR THE |
| | DOWELS AND THE SPACING OF THE DOWELS ON CENTER. |
| | -AS NEW FLOOR PENETRATIONS ARE TO BE MADE FOR THE |
| | FUTURE SHOWER DRAINS AND AS PREVIOUSLY NOTED BY THE |
| | BUILDING PLANS EXAMINER, PER WPB FBC 107.2.1, SHOW |
| | COMPLIANCE WITH THE 2020 FBC-B SECTION 714.5.1.2. |
| | THROUGH-PENETRATIONS FIRESTOP SYSTEMS (HORIZONTAL |
| | ASSEMBLIES). THROUGH PENETRATIONS SHALL BE PROTECTED BY |
| | A THROUGH PENETRATION FIRESTOP SYSTEM INSTALLED IN |
| | ACCORDANCE WITH ASTM E814 OR UL 1479. THE SYSTEM SHALL |
| | HAVE AN F RATING / T RATING OF NOT LESS THAN 1 HOUR BUT |
| | NOT LESS THAN THE REQUIRED RATING OF THE FLOOR |
| | PENETRATED. |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED |
| | AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS. |
| | PLEASE NOTE THAT WHEN SCANNED DRAWINGS ARE SUBMITTED |
| | WITH CONTRACTOR'S PRINTED NAME, SIGNATURE AND LICENSE |
| | NUMBER IN ACCORDANCE WITH WPB FBC 107.2.1, A PAPER PLAN |
| | WITH WET SIGNATURE SHALL BE PROVIDED TO THE BUILDING |
| | DEPARTMENT FOR HARD RECORD FILE PRIOR TO ISSUANCE OF A |
| | PERMIT. |
| | |