| Plan Review Notes For Permit 21051655 |
| Permit Number |
21051655 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2021-07-15 13:55:26 | CONCRETE FOUNDATION, STAIR HAND AND GUARD RAILS | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected]. | | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | | AMENDMENT | | | | | | CORRECTIONS NEEDED - | | | 1) PLEASE PROVIDE HAND AND GUARD RAIL DETAILS SIGNED BY | | | THE DESIGN PROFESSIONAL SHOWING ALL ATTACHMENT TO THE | | | EXISTING STAIR TO COMPLY WITH FBC 1014 AND 1607.8 | | | 2) PLEASE SHOW OPENINGS IN THE GUARD RAILS TO COMPLY | | | WITH FBC 1015.4 | | | 3) PLEASE SHOW THE HEIGHT OF HAND AND GUARD RAILS TO | | | COMPLY WITH FBC 1015.3 AND 1014.2 | | | 4) PLEASE SHOW HAND RAIL EXTENSIONS 1014.6 HANDRAIL | | | EXTENSIONS. | | | HANDRAILS SHALL RETURN TO A WALL, GUARD OR THE WALKING | | | SURFACE OR SHALL BE CONTINUOUS TO THE HANDRAIL OF AN | | | ADJACENT FLIGHT OF STAIRS OR RAMP RUN. WHERE HANDRAILS | | | ARE NOT CONTINUOUS BETWEEN FLIGHTS, THE HANDRAILS SHALL | | | EXTEND HORIZONTALLY NOT LESS THAN 12 INCHES (305 MM) | | | BEYOND THE TOP RISER AND CONTINUE TO SLOPE FOR THE | | | DEPTH OF ONE TREAD BEYOND THE BOTTOM RISER. |
|