Plan Review Notes
Plan Review Notes For Permit 21051652
Permit Number 21051652
Review Stop P
Sequence Number 1
Notes
Date Text
2021-06-16 08:31:401ST REVIEW FBC-2020 PLUMBING
 PERMIT- 21051652
 6/15/21
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEETS P2.0 & P3.0: THE FLOOR DRAIN IN THE STG 114
 REQUIRES AN INDIVIDUAL VENT BECAUSE IT CANNOT BE PART
 OF THE BATHROOM WET VENT SYSTEM- SECTION 912.1 FBC P.
  
 2) P1.0 & P3.0: RELOCATE THE FLOOR DRAIN FROM BELOW THE
 WATER HEATER- SECTION 504.7 FBC P.
  
 3) P4.0: PROVIDE A PAN AND PAN DRAIN FOR THE WATER
 HEATER- SECTION 504.7 FBC P.
  
 4) P4.0: PROVIDE THE EFFICIENCY RATING OF THE WATER
 HEATER- TABLE C404.2 FBC EC.
  
 5) P1.0: PROVIDE A SLAB REPAIR DETAIL- SECTION 107.2.1
 WPB.
  
 6) A3.1.2: IT IS ACKNOWLEDGED THAT THE NEW BATHROOM IS
 FOR PRIVATE AND PUBLIC USE, HOWEVER COMPLIANCE WITH THE
 FBC-2020 ACC CODE IN SPECIFIC AREAS IS REQUIRED AS
 OUTLINED BELOW. PLEASE PROVIDE THESE MISSING COMPLIANCE
 DETAILS:
 A) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE
 WATER CLOSET- SECTION 604.3.
 B) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE
 LAVATORY- SECTION 606.2.
 C) TURNING SPACE DIAGRAM AND DIMENSIONS- SECTION 304.3.
 D) THE LENGTHS OF THE GRAB BAR REINFORCEMENTS FOR THE
 WATER CLOSETS- FIGURES 604.5.1 & 604.5.2.
 E) HEIGHT OF THE MIRROR FROM THE FINISHED FLOOR TO THE
 REFLECTIVE SURFACE- SECTION 603.3
 F) LENGTH MEASUREMENT OF THE SHOWER- SECTION 608.2.2
 G) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE
 SHOWER- SECTION 608.2.1
 H) LOCATIONS AND LENGTHS OF GRAB BAR REINFORCEMENTS FOR
 THE SHOWER- FIGURES 608.3.2 & 608.5.2.
 I) LOCATION OF CONTROL, FAUCET, AND SHOWER SPRAY IN THE
 SHOWER- SECTION 608.5.1.
 J) SHOWER SPRAY UNIT SPECIFICATIONS PER SECTION 608.6.
 K) GRAB BAR REINFORCEMENT DETAIL SHOWING THE TYPE OF
 REINFORCEMENT MATERIALS TO BE INSTALLED, THE WIDTH AND
 THICKNESSES OF THE MATERIAL, FASTENING DETAILS- SEE
 SECTION 609.8.
  
 7) A5.1.1 DETAIL 16/A5.1.1: THE SHOWER PAN LINER SHALL
 BE PITCHED ONE-FOURTH UNIT VERTICAL IN 12 UNITS
 HORIZONTAL (2-PERCENT SLOPE). PLEASE CORRECT THE 1/8-
 INCH PER FT. SLOPE NOTE- SECTION 421.5.2 FBC P.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  