| 2021-06-16 08:31:40 | 1ST REVIEW FBC-2020 PLUMBING |
| | PERMIT- 21051652 |
| | 6/15/21 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 |
| | FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 |
| | FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| | 2020 |
| | FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEETS P2.0 & P3.0: THE FLOOR DRAIN IN THE STG 114 |
| | REQUIRES AN INDIVIDUAL VENT BECAUSE IT CANNOT BE PART |
| | OF THE BATHROOM WET VENT SYSTEM- SECTION 912.1 FBC P. |
| | |
| | 2) P1.0 & P3.0: RELOCATE THE FLOOR DRAIN FROM BELOW THE |
| | WATER HEATER- SECTION 504.7 FBC P. |
| | |
| | 3) P4.0: PROVIDE A PAN AND PAN DRAIN FOR THE WATER |
| | HEATER- SECTION 504.7 FBC P. |
| | |
| | 4) P4.0: PROVIDE THE EFFICIENCY RATING OF THE WATER |
| | HEATER- TABLE C404.2 FBC EC. |
| | |
| | 5) P1.0: PROVIDE A SLAB REPAIR DETAIL- SECTION 107.2.1 |
| | WPB. |
| | |
| | 6) A3.1.2: IT IS ACKNOWLEDGED THAT THE NEW BATHROOM IS |
| | FOR PRIVATE AND PUBLIC USE, HOWEVER COMPLIANCE WITH THE |
| | FBC-2020 ACC CODE IN SPECIFIC AREAS IS REQUIRED AS |
| | OUTLINED BELOW. PLEASE PROVIDE THESE MISSING COMPLIANCE |
| | DETAILS: |
| | A) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE |
| | WATER CLOSET- SECTION 604.3. |
| | B) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE |
| | LAVATORY- SECTION 606.2. |
| | C) TURNING SPACE DIAGRAM AND DIMENSIONS- SECTION 304.3. |
| | D) THE LENGTHS OF THE GRAB BAR REINFORCEMENTS FOR THE |
| | WATER CLOSETS- FIGURES 604.5.1 & 604.5.2. |
| | E) HEIGHT OF THE MIRROR FROM THE FINISHED FLOOR TO THE |
| | REFLECTIVE SURFACE- SECTION 603.3 |
| | F) LENGTH MEASUREMENT OF THE SHOWER- SECTION 608.2.2 |
| | G) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE |
| | SHOWER- SECTION 608.2.1 |
| | H) LOCATIONS AND LENGTHS OF GRAB BAR REINFORCEMENTS FOR |
| | THE SHOWER- FIGURES 608.3.2 & 608.5.2. |
| | I) LOCATION OF CONTROL, FAUCET, AND SHOWER SPRAY IN THE |
| | SHOWER- SECTION 608.5.1. |
| | J) SHOWER SPRAY UNIT SPECIFICATIONS PER SECTION 608.6. |
| | K) GRAB BAR REINFORCEMENT DETAIL SHOWING THE TYPE OF |
| | REINFORCEMENT MATERIALS TO BE INSTALLED, THE WIDTH AND |
| | THICKNESSES OF THE MATERIAL, FASTENING DETAILS- SEE |
| | SECTION 609.8. |
| | |
| | 7) A5.1.1 DETAIL 16/A5.1.1: THE SHOWER PAN LINER SHALL |
| | BE PITCHED ONE-FOURTH UNIT VERTICAL IN 12 UNITS |
| | HORIZONTAL (2-PERCENT SLOPE). PLEASE CORRECT THE 1/8- |
| | INCH PER FT. SLOPE NOTE- SECTION 421.5.2 FBC P. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL/PLUMBING PLANS EXAMINER |