| 2021-06-04 14:45:07 | 1ST REVIEW FBC-2020 MECHANICAL |
| | PERMIT-21051630 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE |
| | FBC M- FLORIDA MECHANICAL CODE |
| | FBC EC- FLORIDA ENERGY CONSERVATION |
| | FBC FG- FLORIDA FUEL GAS |
| | FBC EX- FLORIDA EXISTING BUILDING CODE |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) THE MECHANICAL EQUIPMENT SIZING CALCULATIONS REQUIRE |
| | VARIABLE AIR VOLUME DEVICES FOR THIS PROJECT. PLEASE |
| | SHOW THESE ON THE DRAWING. |
| | |
| | 2) PLEASE PROVIDE A MECHANICAL DRAWING SHOWING THE |
| | NAMES OF EACH SPACE IN THE BUILDING. FBC 107.2.1 |
| | |
| | 3) IT APPEARS FROM THE DRAWING THAT THE CONDENSING |
| | UNITS ARE LOCATED IN THE PARKING LOT, PLEASE SHOW HOW |
| | YOU WILL PROVIDE PROTECTION FROM DAMAGE FOR THESE |
| | UNITS. FBC M 303.4 |
| | |
| | 4) PLEASE SHOW THE CONDENSATION PIPING MATERIAL AND THE |
| | TERMINATION LOCATION. FBC M 307 |
| | |
| | 5) PLEASE PROVIDE OUTDOOR AIR CALCULATIONS BASED OFF OF |
| | THE 2020 FBC M 403.3.1.1 AND TABLE 403.3.1.1 FOR EACH |
| | SPACE OF THE TENANT SPACE. |
| | |
| | 6) THE DESIGNER OF THE DRAWING MUST INCLUDE THE ADDRESS |
| | THE WORK IS BEING INSTALLED, THEIR NAME AND THEIR |
| | SIGNATURE. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM. |
| | |