| 2021-06-18 15:35:49 | 06/18/21 1ST LP GAS REVIEW**DENIED** WITH COMMENTS |
| | |
| | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| | TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| | |
| | 1. PLEASE PROVIDE A RISER DIAGRAM WHICH IS REQUIRED PER |
| | THE WPB AMENDMENTS TO THE FBC SEC. 107.3.5.3 (12) |
| | RESIDENTIAL GAS. SHOW THE TYPE OF PIPE MATERIAL BEING |
| | INSTALLED, ALL PIPE SIZES, AND). IN ADDITION, SHOW ON |
| | THE ISOMETRIC DRAWING THE LENGTH OF ALL CUT SECTIONS OF |
| | PIPE PER 2020 FBC RES. SECS. G2413.4.1, G2413.4.2. |
| | PLEASE SHOW EXISTING GAS EQUIPMENT ON ISOMETRIC. |
| | |
| | 2. THERE IS AN EXISTING GAS, PLEASE LIST THE BTU LOAD |
| | OF EACH APPLIANCE AND THE TOTAL BTU LOAD ON THE SYSTEM. |
| | REFER TO THE OR 2020 FBC RES. SEC. G2413. THE EXISTING |
| | GAS SYSTEM MUST BE ADDED INTO THE TOTAL BTU LOAD ON THE |
| | SYSTEM TO ENSURE THE EXISTING SYSTEM IS PROPERLY SIZED. |
| | IF UNDERSIZED, THE EXISTING SYSTEM MUST BE REDONE TO |
| | ENSURE A SAFE OPERATING SYSTEM. SUBMIT A GAS PIPING |
| | RISER DIAGRAM THAT SHOWS THE TYPE OF EXISTING |
| | APPLIANCE, THE BTU LOAD OF EACH APPLIANCE, THE PIPE |
| | SIZE AND TYPE OF PIPE TO EACH APPLIANCE, AND THE |
| | DISTANCE OF THE LONGEST LENGTH OF PIPING FROM THE POINT |
| | OF DELIVERY TO THE MOST REMOTE OUTLET AND THE LOAD OF |
| | THE SECTION. |
| | |
| | 3. PLEASE SUBMIT MANUFACTURER'S SPECIFICATION |
| | SHEETS/INSTALLATION MANUAL FOR THE GENERATORS TO VERIFY |
| | COMPLIANCE WITH 2017 FBC FG SEC.305.1 OR 2017 FBC RES. |
| | SEC. G2408.1. |
| | |
| | 4. PLEASE SHOW AND LABEL ALL UNIONS IN FRONT OF |
| | REGULATOR 1' OF EITHER SIDE, DRIP LEG, AND SHUTOFF |
| | VALVE PER THE 2020 FBC RES. SEC G2421.2. |
| | |
| | 5. PLEASE LABEL THE SHUTOFF VALVE ON GAS ISOMERIC PER |
| | THE 2020 FBC RES. SEC. G2420.5. |
| | |
| | 6. THE GENERATOR EXHAUST IS REQUIRED TO BE 10 FEET |
| | FROM OPENINGS INTO A BUILDING. FBC-R303.5.1 INTAKE |
| | OPENINGS. MECHANICAL AND GRAVITY OUTDOOR AIR INTAKE |
| | OPENINGS SHALL BE LOCATED NOT LESS THAN 10 FEET (3048 |
| | MM) FROM ANY HAZARDOUS OR NOXIOUS CONTAMINANTS, SUCH AS |
| | VENTS, CHIMNEYS, PLUMBING VENTS, STREETS, ALLEYS, |
| | PARKING LOTS, AND LOADING DOCKS. PLEASE SHOW ON PLANS |
| | PERT THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1 |
| | INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA |
| | LUIS A. CRESPO |
| | PLUMBING PLAN EXAMINER / INSPECTOR |
| | EMAIL: [email protected] OFFICE: 561 805-6720 |
| | |