| 2021-06-14 09:14:55 | 1ST REVIEW FBC-2020 MECHANICAL |
| | PERMIT-21051514 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE |
| | FBC M- FLORIDA MECHANICAL CODE |
| | FBC EC- FLORIDA ENERGY CONSERVATION |
| | FBC FG- FLORIDA FUEL GAS |
| | FBC EX- FLORIDA EXISTING BUILDING CODE |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) PLEASE PROVIDE OUTDOOR AIR CALCULATIONS FOR EACH |
| | SPACE IN THIS TENANT SPACE BASED ON FBC M 403.3.1.1 AND |
| | TABLE 403.3.1.1 AND NOT THE ARCHITECTURAL OCCUPANT |
| | LOAD. RTU 1&5 DINING AREA OUTDOOR AIR SHOULD BE 952 |
| | CFM; RTU?S 2,3&4 OUTDOOR AIR SHOULD BE 1452 CFM. |
| | |
| | 403.3.1.1OUTDOOR AIRFLOW RATE. |
| | VENTILATION SYSTEMS SHALL BE DESIGNED TO HAVE THE |
| | CAPACITY TO SUPPLY THE MINIMUM OUTDOOR AIRFLOW RATE, |
| | DETERMINED IN ACCORDANCE WITH THIS SECTION. IN EACH |
| | OCCUPIABLE SPACE, THE VENTILATION SYSTEM SHALL BE |
| | DESIGNED TO DELIVER THE REQUIRED RATE OF OUTDOOR |
| | AIRFLOW TO THE BREATHING ZONE. THE OCCUPANT LOAD |
| | UTILIZED FOR DESIGN OF THE VENTILATION SYSTEM SHALL BE |
| | NOT LESS THAN THE NUMBER DETERMINED FROM THE ESTIMATED |
| | MAXIMUM OCCUPANT LOAD RATE INDICATED IN TABLE |
| | 403.3.1.1. VENTILATION RATES FOR OCCUPANCIES NOT |
| | REPRESENTED IN TABLE 403.3.1.1 SHALL BE THOSE FOR A |
| | LISTED OCCUPANCY CLASSIFICATION THAT IS MOST SIMILAR IN |
| | TERMS OF OCCUPANT DENSITY, ACTIVITIES AND BUILDING |
| | CONSTRUCTION; OR SHALL BE DETERMINED BY AN APPROVED |
| | ENGINEERING ANALYSIS. THE VENTILATION SYSTEM SHALL BE |
| | DESIGNED TO SUPPLY THE REQUIRED RATE OF VENTILATION AIR |
| | CONTINUOUSLY DURING THE PERIOD THE BUILDING IS |
| | OCCUPIED, EXCEPT AS OTHERWISE STATED IN OTHER |
| | PROVISIONS OF THE CODE. |
| | |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM. |
| | |