| 2021-08-04 08:05:44 | 2ND REVIEW FBC-2020 MECHANICAL |
| | PERMIT-21051507 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE |
| | FBC M- FLORIDA MECHANICAL CODE |
| | FBC EC- FLORIDA ENERGY CONSERVATION |
| | FBC FG- FLORIDA FUEL GAS |
| | FBC EX- FLORIDA EXISTING BUILDING CODE |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) IS THIS A LIKE FOR LIKE CHANGE OUT? IF SO PLEASE |
| | PROVIDE THE LIKE FOR LIKE CHANGE OUT FORM SHOWING THE |
| | OUT UNIT INFORMATION. IF NOT PLEASE PROVIDE THE |
| | MECHANICAL EQUIPMENT SIZING CALCULATIONS SIGNED BY THE |
| | MECHANICAL CONTRACTOR OR A LICENSED ENGINEER CAN |
| | DIGITALLY SIGN THE DOCUMENTS. FBC 107.2.1 |
| | |
| | 2) PLEASE SHOW THE RETURN AIR PATH FROM BEDROOMS 1 AND |
| | 2 TO THE AHU. FBC RES M1602.3 |
| | |
| | 3) PLEASE SHOW THE CONDENSING UNIT TIE DOWN. FBC RES |
| | M1307.2 |
| | |
| | 4) IS THE HOOD VENTED TO THE EXTERIOR? FBC RES M1503 |
| | |
| | 5) PLEASE SHOW THE DRYER DUCT AND TERMINATION LOCATION. |
| | FBC RES M1502.3 |
| | |
| | 6) PLEASE SHOW THE CONDENSATION PIPING AND TERMINATION |
| | LOCATION. FBC RES M1411.3 |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM. |
| | |