Plan Review Notes
Plan Review Notes For Permit 21051505
Permit Number 21051505
Review Stop G
Sequence Number 1
Notes
Date Text
2021-06-01 11:39:5606/01/21 1ST GAS REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
  
 1. THE PHYSICAL ADDRESS OF THE PROJECT MUST BE ON PLANS
 IN FULL, NUMBER, STREET, CITY, STATE, AND ZIP CODE PER
 THE WPB AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION
 ON CONSTRUCTION DOCUMENTS.
  
 2. THE BTU FOR THE GENERATOR IS 327 BTU'S AND
 MANUFACTURES IS 306 BTIU'S, PLEASE CORRECT PER THE WPB
 AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 3. SHOW THE DISTANCE FROM THE POINT OF DELIVERY, (GAS
 METER / MP REGULATOR / LP TANK) TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER THE 2020 FBC
 RES. SEC. G2413.4.1.
  
 4. SUBMIT MANUFACTURERSS SPECIFICATION
 SHEETS/INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO
 VERIFY COMPLIANCE WITH 2020 FBC RES. SEC. G2408.1.
  
 5. GAS APPLIANCES SHALL BE LISTED AND LABELED. THE
 INSTALLATION MANUALS FOR ALL GAS APPLIANCES/EQUIPMENT
 SHALL BE ONSITE AT THE TIME OF INSPECTION PER THE 2020
 FBC RES. SEC. G2413.2 AND G2404.3.
  
 6. INDICATE ON THE PLAN IF THE GRILL IS LOCATED UNDER A
 ROOF PER THE WPB AMENDMENTS TO FBC SEC. 107.2.1.
  
 7. IF THE GRILL IS IN A COVERED PATIO, PLEASE PROVIDE
 MANUFACTURES RECOMMENDATION FOR A VENTILATION HOOD PER
 THE 2020 FBC RES. SEC.G2408.1.
  
 8. SUBMIT MANUFACTURES SPECIFICATIONS FOR THE PRESSURE
 REGULATORS. REGULATORS INSTALLED ON THE EXTERIOR OF THE
 BUILDING SHALL BE APPROVED FOR OUTDOOR INSTALLATION PER
 THE 2020 FBC RES. SEC. G2421.1.
  
 9. PLEASE SHOW AND LABEL ALL UNIONS IN FRONT OF
 REGULATOR 1' OF EITHER SIDE PER THE 2020 FBC RES. SEC
 G2421.2.
  
 10. PLEASE LABEL THE DRIP LEGS AND SHUTOFF VALVE ON GAS
 ISOMERIC PER THE 2020 FBC RES. SEC. G2420.5.
  
 11. THE CLAIMED VALUE APPEARS TO BE UNDERESTIMATED ON
 THE APPLICATION, PLEASE PROVIDE A BONA FIDE SIGNED
 CONTRACT PER THE WPB AMENDMENTS TO THE FBC 109.3.
 BUILDING PERMITS VALUATIONS. IF IN THE OPINION OF THE
 BUILDING OFFICIAL, THE CLAIMED VALUATION OF THE
 BUILDING, ALTERATION, STRUCTURE, ELECTRICAL, GAS,
 MECHANICAL, OR PLUMBING SYSTEMS APPEARS TO BE
 UNDERESTIMATED ON THE APPLICATION, THE PERMIT SHALL BE
 DENIED UNLESS THE APPLICANT CAN SHOW DETAILED, QUANTITY
 ESTIMATES, AND/OR BONA FIDE SIGNED CONTRACTS (EXCLUDING
 LAND VALUE) TO MEET THE APPROVAL OF THE BUILDING
 OFFICIAL. FOR PERMITTING PURPOSES, THE VALUATION OF
 BUILDINGS AND SYSTEMS SHALL BE TOTAL REPLACEMENT VALUE
 TO INCLUDE STRUCTURAL, ELECTRIC, PLUMBING, MECHANICAL,
 INTERIOR FINISH, RELATIVE SITE WORK, ARCHITECTURAL AND
 DESIGN FEES, MARKETING COSTS, OVERHEAD, AND PROFIT;
 EXCLUDING ONLY LAND VALUE. VALUATION REFERENCES MAY
 INCLUDE THE LATEST PUBLISHED DATA OF NATIONAL
 CONSTRUCTION COST ANALYSIS SERVICES (MARSHALL-SWIFT,
 MEANS, ETC.), AS PUBLISHED BY INTERNATIONAL CODE
 CONGRESS. THE FINAL BUILDING PERMIT VALUATION SHALL BE
 SET BY THE BUILDING OFFICIAL.
  
 12. PLEASE CLOUD GENERATOR AN PUT NOTE THAT A SEPARATE
 PERMIT WILL BE DONE FOR INSTALLATION BY A LICENSED
 CONTRACTOR PER THE WPB AMENDMENTS TO THE FBC SEC.
 105.1.
  
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION,
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND, WILL HELP EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720