| Plan Review Notes For Permit 21051502 |
| Permit Number |
21051502 |
|
| Review Stop |
M |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2021-10-28 12:32:12 | PLEASE SEE PREVIOUS COMMENTS 1 AND 3 BELOW. I DO NOT | | | SEE ANYTHING ON SHEET M1-01A ABOUT THE FUEL PIPING | | | SYSTEM. PLEASE SHOW A DRAWING INDICATING THE PIPING | | | MATERIAL, SIZE AND ROUTE FROM THE FILL LOCATION TO THE | | | TANK INCLUDING ALL SHUT-OFF VALVES. FBC M 1305 | | | | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) SHEET M1.01A: PLEASE SHOW THE FUEL PIPING ON THE | | | DRAWING. FBC M 1305 | | | | | | 3) THE FUEL OIL SUPPLY LINE SHALL HAVE A BUILDING SHUT | | | OFF. FBC M 1307.1 | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|