| 2021-07-30 13:01:28 | 1ST REVIEW FBC-2020 MECHANICAL | | | PERMIT-21051502 | | | | | | CODES IN EFFECT: | | | | | | FBC B- FLORIDA BUILDING CODE | | | FBC M- FLORIDA MECHANICAL CODE | | | FBC EC- FLORIDA ENERGY CONSERVATION | | | FBC FG- FLORIDA FUEL GAS | | | FBC EX- FLORIDA EXISTING BUILDING CODE | | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) SHEET M1.01A: PLEASE SHOW THE FUEL PIPING ON THE | | | DRAWING. FBC M 1305 | | | | | | 2) VENT PIPING MUST MEET TERMINATION PROTECTION OF FBC | | | M 1305.7 | | | | | | 3) THE FUEL OIL SUPPLY LINE SHALL HAVE A BUILDING SHUT | | | OFF. FBC M 1307.1 | | | | | | 4) PLEASE PROVIDE INFORMATION ON THE EXHAUST SILENCER. | | | FBC 107.2.1 | | | | | | 5) PLEASE PROVIDE INSTALLATION INSTRUCTIONS FOR THE | | | VENTING OF THE FIRE PUMP. FBC 107.2.1 | | | | | | 6) PLEASE PROVIDE INFORMATION ON THE FUEL TANK. FBC M | | | 1301.4 | | | | | | 7) PLEASE CONTACT DERM TO DETERMINE IF APPROVAL BY THEM | | | IS REQUIRED. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|