Plan Review Notes
Plan Review Notes For Permit 21051502
Permit Number 21051502
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2021-07-16 16:02:14THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THERE ARE INDICATIONS OF THE VENTS TERMINATING AT
 THE 2ND FLOOR LEVEL OF THE PARKING GARAGE.
  
 ADDITIONALLY, PLEASE PROVIDE DETAILS OR SPECS THAT THE
 3" PIPE SIZE IS SUFFIENCT FOR THIS TANK.
  
 PER NFPA 110
  
 7.10.2 EXHAUST SYSTEM INSTALLATION SHALL BE GASTIGHT TO
 PREVENT
 EXHAUST GAS FUMES FROM ENTERING INHABITED ROOMS OR
 BUILDINGS
 AND TERMINATE IN SUCH A MANNER THAT TOXIC FUMES CANNOT
 REENTER A BUILDING OR STRUCTURE, PARTICULARLY THROUGH
 WINDOWS,
 AIR VENTILATION INLETS, OR THE ENGINE AIR-INTAKE
 SYSTEM.
  
 PER NFPA 30
  
 22.6 VENT PIPING FOR ABOVEGROUND TANKS. PIPING FOR
 NORMAL
 AND EMERGENCY RELIEF VENTING SHALL BE CONSTRUCTED IN
 ACCORDANCE
 WITH CHAPTER 27.
  
 27.8.1 VENT PIPING FOR ABOVEGROUND STORAGE TANKS.
 27.8.1.1 WHERE THE OUTLETS OF VENT PIPES FOR TANKS
 STORING
 CLASS I LIQUIDS ARE ADJACENT TO BUILDINGS OR PUBLIC
 WAYS, THEY
 SHALL BE LOCATED SO THAT VAPORS ARE RELEASED AT A SAFE
 POINT
 OUTSIDE OF BUILDINGS AND NOT LESS THAN 12 FT (3.6 M)
 ABOVE THE
 ADJACENT GROUND LEVEL.
 27.8.1.2 VAPORS SHALL BE DISCHARGED UPWARD OR
 HORIZONTALLY
 AWAY FROM ADJACENT WALLS.
 27.8.1.3 VENT OUTLETS SHALL BE LOCATED SO THAT VAPORS
 WILL NOT BE
 TRAPPED BY EAVES OR OTHER OBSTRUCTIONS AND SHALL BE AT
 LEAST 5 FT
 (1.5 M) FROM BUILDING OPENINGS AND AT LEAST 15 FT (4.5
 M) FROM
 POWERED VENTILATION AIR INTAKE DEVICES.
  
 PLEASE REVIEW AND PROVIDE DETAILS FOR COMPLIANCE OR
 CORRECT.
  
  
 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  
  
 7.10.2 EXHAUST SYSTEM INSTALLATION SHALL BE GASTIGHT TO
 PREVENT
 EXHAUST GAS FUMES FROM ENTERING INHABITED ROOMS OR
 BUILDINGS
 AND TERMINATE IN SUCH A MANNER THAT TOXIC FUMES CANNOT
 REENTER A BUILDING OR STRUCTURE, PARTICULARLY THROUGH
 WINDOWS,
 AIR VENTILATION INLETS, OR THE ENGINE AIR-INTAKE
 SYSTEM.