| 2021-07-16 16:02:14 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | |
| | 1) THERE ARE INDICATIONS OF THE VENTS TERMINATING AT |
| | THE 2ND FLOOR LEVEL OF THE PARKING GARAGE. |
| | |
| | ADDITIONALLY, PLEASE PROVIDE DETAILS OR SPECS THAT THE |
| | 3" PIPE SIZE IS SUFFIENCT FOR THIS TANK. |
| | |
| | PER NFPA 110 |
| | |
| | 7.10.2 EXHAUST SYSTEM INSTALLATION SHALL BE GASTIGHT TO |
| | PREVENT |
| | EXHAUST GAS FUMES FROM ENTERING INHABITED ROOMS OR |
| | BUILDINGS |
| | AND TERMINATE IN SUCH A MANNER THAT TOXIC FUMES CANNOT |
| | REENTER A BUILDING OR STRUCTURE, PARTICULARLY THROUGH |
| | WINDOWS, |
| | AIR VENTILATION INLETS, OR THE ENGINE AIR-INTAKE |
| | SYSTEM. |
| | |
| | PER NFPA 30 |
| | |
| | 22.6 VENT PIPING FOR ABOVEGROUND TANKS. PIPING FOR |
| | NORMAL |
| | AND EMERGENCY RELIEF VENTING SHALL BE CONSTRUCTED IN |
| | ACCORDANCE |
| | WITH CHAPTER 27. |
| | |
| | 27.8.1 VENT PIPING FOR ABOVEGROUND STORAGE TANKS. |
| | 27.8.1.1 WHERE THE OUTLETS OF VENT PIPES FOR TANKS |
| | STORING |
| | CLASS I LIQUIDS ARE ADJACENT TO BUILDINGS OR PUBLIC |
| | WAYS, THEY |
| | SHALL BE LOCATED SO THAT VAPORS ARE RELEASED AT A SAFE |
| | POINT |
| | OUTSIDE OF BUILDINGS AND NOT LESS THAN 12 FT (3.6 M) |
| | ABOVE THE |
| | ADJACENT GROUND LEVEL. |
| | 27.8.1.2 VAPORS SHALL BE DISCHARGED UPWARD OR |
| | HORIZONTALLY |
| | AWAY FROM ADJACENT WALLS. |
| | 27.8.1.3 VENT OUTLETS SHALL BE LOCATED SO THAT VAPORS |
| | WILL NOT BE |
| | TRAPPED BY EAVES OR OTHER OBSTRUCTIONS AND SHALL BE AT |
| | LEAST 5 FT |
| | (1.5 M) FROM BUILDING OPENINGS AND AT LEAST 15 FT (4.5 |
| | M) FROM |
| | POWERED VENTILATION AIR INTAKE DEVICES. |
| | |
| | PLEASE REVIEW AND PROVIDE DETAILS FOR COMPLIANCE OR |
| | CORRECT. |
| | |
| | |
| | 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |
| | 561-804-4709 |
| | [email protected] |
| | |
| | |
| | |
| | 7.10.2 EXHAUST SYSTEM INSTALLATION SHALL BE GASTIGHT TO |
| | PREVENT |
| | EXHAUST GAS FUMES FROM ENTERING INHABITED ROOMS OR |
| | BUILDINGS |
| | AND TERMINATE IN SUCH A MANNER THAT TOXIC FUMES CANNOT |
| | REENTER A BUILDING OR STRUCTURE, PARTICULARLY THROUGH |
| | WINDOWS, |
| | AIR VENTILATION INLETS, OR THE ENGINE AIR-INTAKE |
| | SYSTEM. |