Plan Review Notes
Plan Review Notes For Permit 21051470
Permit Number 21051470
Review Stop P
Sequence Number 1
Notes
Date Text
2021-06-03 11:52:2605/04/21 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. PLEASE SUBMIT TOTAL DYNAMIC HEAD CALCULATIONS FOR
 THE MAXIMUM SYSTEM FLOW. THE TDH CALCULATIONS MUST
 INCLUDE ALL THE SYSTEM COMPONENTS, INCLUDING SUCTION
 AND RETURN PIPING, FITTINGS, VALVES, HEATER, AND
 FILTER. ALL SYSTEM COMPONENTS EXCEPT THE PUMP.
  
 2. PLEASE THE POOL PUMP CURVE. IDENTIFY ON THE PUMP
 CURVE WHICH CURVE KEY IS SPECIFIC TO THE PUMP BEING
 INSTALLED ON THIS POOL. THIS IS NEEDED TO CONFIRM THE
 MAXIMUM SYSTEM FLOW FROM THE TDH CALCULATIONS PER THE
 ANSI/APSP/ICC 7 - 2013 SECS. 4.4.9, 4.4.9.1. INDICATE
 ON THE PUMP CURVE WHICH CURVE KEY IS FOR THE PUMP BEING
 INSTALLED ON THIS SYSTEM PER THE WPB AMEND. TO FBC SEC.
 107.2.1.
  
 3. PLEASE SUBMIT THE MANUFACTURER'S SPECIFICATIONS FOR
 THE FILTER, AND PUMP PER THE WPB AMENDMENTS TO FBC SEC.
 107.2.1.
  
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND, WILL HELP EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  