| Plan Review Notes For Permit 21051408 |
| Permit Number |
21051408 |
|
| Review Stop |
Z |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2021-06-16 13:33:56 | FAILED | | | | | | PROVIDE WRITTEN RESPONSE TO COMMENTS. | | | | | | 1) THE CIVIL PLANS SHOW A RECONFIGURATION OF THE | | | SERVICE AREA BEHIND TENANT B05. THE RECONFIGURATION | | | INCLUDES THE REMOVAL OF TWO DUMPSTERS AND THE | | | INSTALLATION OF ONE REPLACEMENT DUMPSTER. THIS | | | RECONFIGURATION REQUIRES THE APPROVAL OF A MINOR | | | PLANNED DEVELOPMENT AMENDMENT PRIOR TO THE APPROVAL OF | | | THIS PERMIT BY ZONING. THE MINOR PD AMENDMENT SHALL | | | INCLUDE THE CHANGES THAT WERE DISCUSSED WITH PERMIT | | | 21040663 (AVALON SPACE) INCLUDING WHAT IS SHOWN ON | | | SHEET A100.1 OF THIS PERMIT SUBMITTAL. NOTE: THE | | | DUMPSTER RELOCATION REQUIRES THE SUBMITTAL AND APPROVAL | | | OF A SEPARATE DUMPSTER ENCLOSURE PERMIT TO THE BUILDING | | | DIVISION. | | | | | | 2) THANK YOU FOR PROVIDING THE SITE LINE DRAWING FOR | | | THE NEW ROOFTOP EQUIPMENT. PLEASE ADD THE DIMENSIONS | | | FOR THE FULL HEIGHT, INCLUDING CURB, FOR THE NEW | | | ROOFTOP MECHANICAL EQUIPMENT AS WELL AS THE ROOF AND | | | PARAPET HEIGHTS TO THE DRAWINGS. | | | | | | 3) PLEASE EXPLAIN WHY THE ROOF PLAN (SHEET A210) AND | | | THE MECHANICAL ROOF PLAN (SHEET M201) SHOW DIFFERENT | | | LOCATIONS FOR THE ROOFTOP EQUIPMENT. | | | | | | CONTACT ERIC SCHNEIDER @ (561) 822-1446 | | | [email protected] | | | |
|