| 2021-07-08 09:13:53 | 1ST REVIEW FBC-2020 RES. GAS |
| | PERMIT- 21051400 |
| | 7/8/2021 |
| | |
| | CODES IN EFFECT: |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION |
| | 2020 |
| | FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| | 2020 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) GAS FOR A FUTURE BBQ WAS APPROVED UNDER REVISION |
| | 21021053 TO MASTER 20091091. THE APPROVED DRAWINGS FOR |
| | THOSE PERMITS SHOW A GAS LINE TERMINATING AT THE NW |
| | CORNER OF THE PROPERTY HOWEVER THE PROPOSED GRILL |
| | LOCATION IS SHOWN UNDER A PAVILION LOCATED FURTHER |
| | SOUTH OF THE CORNER. PLEASE PROVIDE A COMPLETE GAS |
| | RISER DRAWING THAT INCLUDES THE TOTAL PIPING RUN FROM |
| | THE NEW TANK TO THE GRILL- SECTIONS G2412.3 & G2412.4 |
| | FBC RES. PLEASE SHOW THE RISER AT THE GRILL LOCATION, |
| | AND THE LOCATIONS OF THE DRIP LEG, SHUT OFF VALVE, |
| | REGULATOR AND PIPE UNIONS- SECTIONS G2419, G2420, |
| | G2421, G2422 FBC RES. |
| | |
| | 2) I RESEARCHED THE USE AND CARE MANUAL FOR THE LYNX |
| | GRILL MODEL L36TR AND ON PAGE 6 THESE WARNINGS FROM THE |
| | MANUFACTURER ARE LISTED- |
| | 6. NEVER LOCATE THE GRILL UNDER A ROOF OR OVERHANG, IN |
| | A BUILDING, GARAGE, SHED OR OTHER SUCH ENCLOSED AREA. |
| | 7. NEVER LOCATE THE GRILL UNDER UNPROTECTED COMBUSTIBLE |
| | CONSTRUCTION. |
| | BASED ON THOSE MANUFACTURER'S WARNINGS AND SECTION |
| | G2447.1 OF THE FBC RES, IT APPEARS THE GRILL MAY NOT BE |
| | SAFELY LOCATED UNDER THE PAVILION. |
| | SECTION G2447.1 COOKING APPLIANCES STATES: |
| | COOKING APPLIANCES THAT ARE DESIGNED FOR PERMANENT |
| | INSTALLATION, INCLUDING RANGES, OVENS, STOVES, |
| | BROILERS, GRILLS, FRYERS, GRIDDLES, HOT PLATES AND |
| | BARBECUES, SHALL BE TESTED IN ACCORDANCE WITH ANSI |
| | Z21.1 OR ANSI Z21.58 AND SHALL BE INSTALLED IN |
| | ACCORDANCE WITH THE MANUFACTURER'S INSTRUCTIONS. |
| | |
| | PLEASE CONSULT WITH THE MANUFACTURER FOR ADDITIONAL |
| | INFORMATION AS TO WHERE THE GRILL CAN BE SAFELY |
| | LOCATED. |
| | |
| | 3) PLEASE CLARIFY IF THE PAVILION IS AN EXISTING OR NEW |
| | STRUCTURE. THE CURRENT PROPERTY APPRAISER'S MAP DOES |
| | NOT APPEAR TO SHOW A PAVILION ON THE LOT. PLEASE NOTE |
| | COMPLETE PLANS UNDER A SEPARATE PERMIT WOULD BE |
| | REQUIRED FOR A NEW STRUCTURE- SECTION 107.2.1 WPB. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |