Plan Review Notes
Plan Review Notes For Permit 21051398
Permit Number 21051398
Review Stop P
Sequence Number 1
Notes
Date Text
2021-12-03 09:04:571ST REVIEW FBC-2020 PLUMBING
 PERMIT- 21051398
 12/2/2021
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET A2.3 FBC ACCESSIBILITY CORRECTIONS:
 A) THE DOOR SHALL NOT SWING INTO THE CLEAR FLOOR SPACE
 REQUIRED FOR THE LAVATORY- SECTION 603.2.3
 B) SHOW A MINIMUM 30X48-INCH CLEAR FLOOR SPACE APPROACH
 AT THE DRINKING FOUNTAIN- 602.2.
 C) SHOW THE SPOUT HEIGHT OF THE DRINKING FOUNTAIN-
 602.4.
 D) SHOW THE REACH RANGE HEIGHT OF THE BOTTLE FILLER-
 SECTION 308
 E) SHOW THE 40-INCH HEIGHT OF THE MIRROR FROM THE
 FINISHED FLOOR TO THE REFLECTIVE SURFACE- SECTION 603.3
 F) SHOW THE LOCATIONS OF THE WATER CLOSET FLUSH CONTROL
 - SECTION 604.6.
 G) SHOW THE 7-INCH MINIMUM AND 9-INCH MAXIMUM
 CENTERLINE OF THE TOILET PAPER DISPENSER MEASURED FROM
 THE FRONT OF THE WATER CLOSETS- SECTION AND FIGURE
 604.7.
 H) IT APPEARS A PARALLEL APPROACH WILL BE USED FOR THE
 KITCHENETTE SINK. PLEASE SHOW A MINIMUM 30X48 INCH
 CLEAR FLOOR SPACE AT THE SINK- 606.2
 I) SHOW THE KNEE AND TOE CLEARANCES FOR THE LAVATORIES-
 SECTION 606.2 & FIGURES 306.2 & 306.3.
 J) SHOW THE WATER CLOSET GRAB BAR MEASUREMENTS TO THE
 TOPS OF THE GRIPPING SURFACES- 609.4.
  
 2) PLEASE CORRECT THE NOTE SPECIFYING PAINTED GYPSUM
 BOARD FOR THE WALLS SURROUNDING THE MOP SINK. IN
 ACCORDANCE WITH SECTION 310.3 FBC P AND 1210.2.2 FBC B-
 WALLS AND PARTITIONS WITHIN 2 FEET OF SERVICE SINKS,
 URINALS AND WATER CLOSETS SHALL HAVE A SMOOTH, HARD,
 NONABSORBENT SURFACE, TO A HEIGHT OF NOT LESS THAN 4
 FEET ABOVE THE FLOOR, AND EXCEPT FOR STRUCTURAL
 ELEMENTS, THE MATERIALS USED IN SUCH WALLS SHALL BE OF
 A TYPE THAT IS NOT ADVERSELY AFFECTED BY MOISTURE. THE
 WPB BUILDING DEPARTMENT DOES NOT ACCEPT PAINTED GYPSUM
 BOARD AS A COMPLIANT MATERIAL. PLEASE PROVIDE TILE,
 FRP, OR OTHER SMOOTH, HARD, NON-ABSORBENT MATERIAL FOR
 THE WALLS.
  
 3) P401, P601: INDICATE HOW TEMPERED WATER WILL BE
 DELIVERED FROM THE LAVATORIES- 419.5 FBC P.
  
 4) P401, P601, P701: THE PLAN SHOWS NON-COMPLIANCE WITH
 SECTION & TABLE C404.5.1 FBC EC. A 1/2 INCH HW PIPE HAS
 A MAXIMUM ALLOWABLE LENGTH OF 2FT. FROM THE NEAREST HOT
 WATER SOURCE TO THE FIXTURE SUPPLY PIPE AT THE
 LAVATORIES. PLEASE PROVIDE EITHER POINT OF USE WATER
 HEATERS AT THE LAVATORIES OR A HOT WATER RECIRCULATION
 PUMP.
  
 5) P401, P601, P801: PLEASE PROVIDE SYMBOLS TO THE
 LOCATIONS OF WATER HAMMER ARRESTORS AND BACKFLOW
 PREVENTERS- SECTIONS 604.9 & 608.3 FBC P.
  
 6) P801: PLEASE PROVIDE THE LISTING STANDARDS FOR THE
 BACKFLOW PREVENTERS SHOWN IN THE SCHEDULE- TABLE 608.3
 FBC P.
  
 7) P701: SHOW THE LOCATION OF THE WATER HEATER
 EXPANSION TANK IN THE DETAIL- SECTION 607.3 FBC P.
  
 8) A1.0: PLEASE SHOW THE WATER AND SEWER CAPPING
 LOCATIONS- SECTION 107.2.1 WPB.
  
 9) PLEASE REVIEW THE GUIDELINES LISTED BELOW FOR
 BUILDING OR PARTIAL BUILDING DEMOLITION AS SOME
 REQUIREMENTS MAY BE APPLICABLE TO THE PROPOSED PROJECT:
  
 DEMOLITION OF A BUILDING.
 THE FOLLOWING ITEMS ARE REQUIRED PRIOR TO ISSUANCE OF A
 DEMO PERMIT PER FLORIDA BUILDING CODE, BUILDING 3303:
  
 UTILITY RELEASE - FLORIDA POWER & LIGHT (ELECTRIC)
 RELEASE OF SERVICE CONFIRMATION
  
 UTILITY RELEASE - FLORIDA PUBLIC UTILITIES (GAS)
 RELEASE OF SERVICE CONFIRMATION
  
 UTILITY RELEASE - CITY OF WEST PALM BEACH WATER
 DEPARTMENT, REQUEST FOR METER PULL, ON THEIR FORM
 "DEMOLITION APPLICATION"
 HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B
 UILDING-PERMIT-FORMS
  
 IF A WATER TRUCK IS DESIRED FOR WATERING DOWN SITE,
 DETAILS WILL BE REQUIRED.
  
 IF A HYDRANT METER OR BACKFLOW PREVENTER IS DESIRED,
 THEN A PARTIAL RELEASE WILL BE NOTED ON THEIR FORM.
 PLEASE NOTE THAT A SEPARATE PERMIT IS REQUIRED FOR AN
 RPZ BACKFLOW PREVENTER DEVICE AT THE PROPERTY, AND THE
 INSTALLATION MUST HAVE A FINAL PASSED INSPECTION
 INCLUDING TESTING AND CERTIFICATION OF THE DEVICE BY
 THE WPB UTILITIES DEPARTMENT PRIOR TO SCHEDULING THE
 FINAL DEMOLITION INSPECTION. FOR FURTHER INFORMATION
 ABOUT THE BACKFLOW PREVENTER PLEASE CONTACT THE
 UTILITIES DEPT. AT 561-822-2244.
 FAX THE COMPLETED "DEMOLITION APPLICATION" FORM TO
 561-822-2183.
  
 SEWER LATERAL CAPPING PERMIT IS REQUIRED (SUBMIT
 APPLICATION TO BUILDING DIVISION); SCHEDULE A FINAL
 PLUMBING #703.
  
 EXTERMINATION LETTER - LETTER FROM A LICENSED PEST
 CONTROL COMPANY STATING THAT DEMOLITION ADDRESS HAS
 BEEN INSPECTED AND/OR TREATED FOR RODENTS.
  
 COMPLETE THE DEMO DEBRIS REMOVAL FORM:
 HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B
 UILDING-PERMIT-FORMS
 IF THE FORM IS NOT AVAILABLE ONLINE, SEND A REQUEST FOR
 THE FORM TO [email protected].
  
 PROVIDE A SITE PLAN OR SURVEY SHOWING LOCATION OF THE
 STRUCTURE(S) TO BE DEMOLISHED, FBC 107.
  
 PROVIDE A STORMWATER POLLUTION PREVENTION PLAN.
  
 PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
 10) PLEASE NOTE THAT A SEPARATE PERMIT IS REQUIRED FOR
 INSTALLATION OF THE POTABLE WATER SERVICE BACKFLOW
 PREVENTER. A FL. LICENSED PLUMBING CONTRACTOR SHALL
 OBTAIN A SEPARATE PERMIT FOR INSTALLATION OF THE
 BACKFLOW PREVENTER IN ACCORDANCE WITH SECTION 105.1 WPB
 AND SEC. 90-33 WPB CODE OF ORDINANCES. THE DEVICE SHALL
 BE TESTED AND CERTIFIED BY THE WPB UTILITIES DEPARTMENT
 PRIOR TO FINAL INSPECTION BY THE BUILDING DEPARTMENT.
 PLEASE CONTACT THE WPB UTILITIES CENTRAL OPERATIONS
 DEPT.AT 561-822-2210 FOR FURTHER INFORMATION.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  