| Plan Review Notes For Permit 21051398 |
| Permit Number |
21051398 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2021-11-22 13:17:32 | PLEASE PROVIDE THE USE OF THIS BUILDING. THE | | | VENTILATION CALCULATIONS INDICATE THE ENTIRE OPEN AREA | | | WILL BE A BREAKROOM. WHERE IS THE BUSINESS FOR THIS | | | BREAKROOM? THE VENTILATION CALCULATION TABLE HAS BOTH | | | THE 2020 FBC MECHANICAL CODE AND THE ASHRAE 62.1 | | | REFERENCED. PLEASE REMOVE ONE AS THE DESIGN WILL EITHER | | | BE COMPLETELY FROM 2020 FBC OR ASHRAE 62.1-2013. FBC | | | 107.2.1 | | | | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | | | | |
|