Plan Review Notes
Plan Review Notes For Permit 21051368
Permit Number 21051368
Review Stop P
Sequence Number 3
Notes
Date Text
2021-08-13 14:11:403RD REVIEW FBC-2020 PLUMBING
 PERMIT- 21051368
 8/13//2021
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED. FAILED COMMENTS FROM 1ST
 AND 2ND REVIEWS ARE LISTED BELOW WITH ADDITIONAL NOTES.
  
 3) FAILED. D1.01 & P1.01: SHOW AREAS OF SLAB DEMOLITION
 AND NEW SINK DRAIN LINES AND POINTS OF CONNECTIONS TO
 THE EXISTING SANITARY SYSTEM- SECTION 107.2.1 WPB. THE
 SUBMITTED EXISTING FLOOR PLAN DOES NOT SHOW A SINK WAS
 PLANNED TO BE INSTALLED WHERE THE NEW SINK BY IS TO BE
 LOCATED ADJACENT TO PATIENT TLT 110 WALL.
  
 4) FAILED. P1.01: PROVIDE A SANITARY DRAINAGE AND VENT,
 AND WATER SUPPLY ISOMETRIC DRAWING FOR INSTALLATION OF
 THE NEW SINK BY PT TLT 110.- SECTION 107.3.5.3.1 AND
 107.2.1 WPB. NOT PROVIDED.
  
 1) FAILED. PLEASE INDICATE HOW THE NEW SINK IN THE
 CORRIDOR BY TLT 119 WILL BE IN COMPLIANCE WITH SECTION
 307.2 PROTRUSION LIMITS- FBC ACC. NOT PROVIDED.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  