| 2021-07-26 14:53:58 | 2ND REVIEW FBC-2020 PLUMBING |
| | PERMIT- 21051368 |
| | 7/26/2021 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 |
| | FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. COMMENTS 2, 3, & 4 FROM |
| | THE 1ST REVIEW STILL EXIST. THE DEMOLITION PLAN (D1.01) |
| | DOES NOT SHOW EXISTING SINKS AT THE NEW SINK LOCATIONS |
| | SO THE SINKS APPEAR TO BE NEW INSTALLATIONS. PLEASE |
| | NOTE SHEET G301 PROVIDES GENERIC TOILET ROOM DETAILS |
| | AND NOT SITE-SPECIFIC SINK DETAILS. |
| | |
| | 2) P1.01: THE NEW SINKS SHALL BE INSTALLED COMPLIANCE |
| | WITH THE FBC- 202 ACCESSIBILITY CODE SECTIONS 212.3, |
| | 606.2 & 606.3. PLEASE PROVIDE DETAILS SHOWING |
| | COMPLIANCE FOR CLEAR FLOOR SPACE FORWARD APPROACHES TO |
| | THE SINKS, SINK RIM HEIGHTS, AND KNEE AND TOE |
| | CLEARANCES. |
| | |
| | 3) D1.01 & P1.01: SHOW AREAS OF SLAB DEMOLITION AND NEW |
| | SINK DRAIN LINES AND POINTS OF CONNECTIONS TO THE |
| | EXISTING SANITARY SYSTEM- SECTION 107.2.1 WPB. |
| | |
| | 4) P1.01: PROVIDE A SANITARY DRAINAGE AND VENT, AND |
| | WATER SUPPLY ISOMETRIC DRAWINGS- SECTION 107.3.5.3.1 |
| | AND 107.2.1 WPB. |
| | |
| | NEW COMMENT. |
| | |
| | 1) PLEASE INDICATE HOW THE NEW SINK IN THE CORRIDOR BY |
| | TLT 119 WILL BE IN COMPLIANCE WITH SECTION 307.2 |
| | PROTRUSION LIMITS- FBC ACC. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |