| Date |
Text |
| 2021-06-29 10:07:42 | WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION |
| | SERVICES/ BUILDING DIVISION |
| | 2020 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 21051366 |
| | ADD: 720 S. SAPODILLA AVE. # 302 |
| | CONT: PALM BEACH CONSTRUCTION & ASSOCAIATES |
| | TEL: 561-441-7493 |
| | E-MAIL: [email protected] |
| | |
| | 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: TUES. JUNE 29TH / 2021 |
| | ACTION: DENIED |
| | |
| | 1) THE SUBMITTED PLANS DO NOT INDICATE WHO THE AUTHOR |
| | IS. CERTIFICATION BY CONTRACTOR. 107.3.4.3. THE |
| | CONTRACTOR (QUALIFIER) THAT CREATED / DREW THE SET OF |
| | PLANS WILL NEED TO IDENTIFY THEMSELVES AS THE AUTHOR OF |
| | THE PLANS. PLEASE PRINT YOUR NAME, SIGN YOUR NAME AND |
| | LICENSE NUMBER FOR THE TRADE YOU ARE LICENSED IN AND |
| | PLANS DRAWN. |
| | 107.3.4.3 CERTIFICATION BY CONTRACTOR. PLEASE NOTE THE |
| | EXCEPTION TO ENGINEERED PLANS UNDER 471.003(H) |
| | ELECTRICAL/ PLUMBING/ MECHANICAL, 481.229(1)(C) |
| | (BUILDING) REQUIRES THE CONTRACTOR FOR THAT TRADE THAT |
| | WILL BE LICENSED IN THAT TRADE, WILL ALSO BE THE |
| | CONTRACTOR THAT DESIGNS THE SYSTEM UNDER THAT TRADE. |
| | THE CONTRACTOR (QUALIFIER) THAT CREATED / DREW THE SET |
| | OF PLANS WILL NEED TO IDENTIFY THEMSELVES AS THE AUTHOR |
| | OF THE PLANS. PLEASE PRINT YOUR NAME, SIGN YOUR NAME |
| | AND LICENSE NUMBER FOR THE TRADE YOU ARE LICENSED IN |
| | AND PLANS DRAWN. |
| | FOR EACH TRADE THE CONTRACTOR RESPONSIBLE FOR THE |
| | DESIGN UNDER THE TRADE LICENSED IN MUST PRINT THEIR |
| | NAME, SIGN THEIR NAME AND LICENSE NUMBER, NOTE THESE |
| | PLANS APPEAR TO BE DRAWN BY ONE INDUVIAL, THEY WOULD |
| | HAVE TO BE LICENSED AS A BUILDING, ELECTRICAL AND |
| | PLUMBING CONTRACTOR TO SUBMIT ALL THESE TRADES UNDER |
| | ONE SHEET. |
| | |
| | 2) DRAWING # 1 INDICATES THE REMODELING OF THE |
| | BATHROOM, PLEASE INDICATE THE FAIR HOUSING GUIDELINE |
| | TYPE A OR B ON THE PLAN. FAIR HOUSING GUIDELINES. FAIR |
| | HOUSING ACT DESIGN AND CONSTRUCTION REQUIREMENTS. FOR |
| | PURPOSES OF THIS SECTION, A COVERED MULTIFAMILY |
| | DWELLING SHALL BE DEEMED TO BE DESIGNED AND CONSTRUCTED |
| | FOR FIRST OCCUPANCY ON OR BEFORE MARCH 13, 1991, IF |
| | THEY ARE OCCUPIED BY THAT DATE OR IF THE LAST BUILDING |
| | PERMIT OR RENEWAL THEREOF FOR THE COVERED MULTIFAMILY |
| | DWELLINGS IS ISSUED BY A STATE, COUNTY OR LOCAL |
| | GOVERNMENT ON OR BEFORE JANUARY 13, 1990. |
| | FAIR HOUSING LETTER AS AN ALTERNATE METHOD. SEE |
| | PROPOSED LETTER LAYOUT BELOW: |
| | PROJECT ADDRESS: ______________________________________ |
| | _____________________ |
| | PERMIT NUMBER: ________________________ |
| | THE OWNER AND DESIGNER OF RECORD ACKNOWLEDGE THAT THE |
| | PROPOSED BATHROOM DESIGN DOES NOT MEET THE REQUIREMENTS |
| | OF THE FAIR HOUSING ACCESSIBILITY GUIDELINES. THE OWNER |
| | AGREES TO REVERT THE UNIT BACK TO COMPLIANCE AT TIME OF |
| | SALE IF SO REQUESTED BY THE BUYER. |
| | |
| | SIGNATURE OF DESIGNER: ______________________________ |
| | PRINTED NAME OF DESIGNER: ___________________________ |
| | |
| | SIGNATURE OF OWNER: ________________________________ |
| | PRINTED NAME OF OWNER: _____________________________ |
| | NOTARY FOR OWNER?S SIGNATURE: |
| | STATE OF FLORIDA, COUNTY OF PALM BEACH |
| | THE FOREGOING INSTRUMENT WAS ACKNOWLEDGED BEFORE ME |
| | THIS _____ DAY OF ________, 20__ BY |
| | ___________________________ WHO IS PERSONALLY KNOWN TO |
| | ME OR WHO HAS PRODUCED: ___________________________ AS |
| | IDENTIFICATION AND WHO DID / DID NOT TAKE AN OATH. |
| | NOTARY SIGNATURE ___________________________________ |
| | NOTARY PRINTED NAME ________________________________ |
| | |
| | 3) THE FLOOR PLAN LABELED DRAWING # 02 INDICATES THE |
| | INSTALLATION OF PROFLEX 90. PLEASE BE SPECIFIC AS TO |
| | WHICH TYPE OF PROFLEX 90 IS TO BE INSTALLED. PROVIDE |
| | FLOOR FINISH MATERIAL, TILE, MARBLE, WOOD VENEERS OR |
| | VINYL FLOORING. 107.2.1.2 ADDITIONAL INFORMATION IS |
| | REQUIRED. |
| | PROFLEX 90 MSC MEGA SOUND CONTROL WE HAVE NO TESTING |
| | REPORTS ON THIS PRODUCT. |
| | PROFLEX SUPER SIM 90 WE HAVE ALL THE TEST REPORTS |
| | REQUIRED FOR THIS PRODUCT IF TILE OF MARBLE IS BEING |
| | INSTALLED. |
| | FLOOR INSULATION/ UNDERLAYMENT (FBC-B 2020) FOR TILE, |
| | STONE, MARBLE, VINYL AND WOOD FLOORING ALL NEED TO HAVE |
| | HAD THE SOUND UNDERLAYMENT TESTED FLOOR ASSEMBLIES TO |
| | THE FOLLOWING STANDARDS AND MEET THE QUALIFICATIONS |
| | LISTED UNDER EACH OF THE STANDARDS FOR A 6 INCH |
| | CONCRETE FLOOR ASSEMBLY/ NO DROPPED CEILING: |
| | PLEASE PROVIDE ALL THREE TEST REPORTS FOR TYPE I AND OR |
| | TYPE II BUILDINGS SHOWING COMPLIANCE WITH: |
| | |
| | 3A) FBC-B 2020 1207.3 STRUCTURE-BORNE SOUND. |
| | FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR |
| | BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA |
| | WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION |
| | CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD |
| | TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E-492. |
| | |
| | 3B) FBC-B 2020 1207.2 AIR-BORNE SOUND. WALLS, |
| | PARTITIONS AND FLOOR/CEILING ASSEMBLIES SEPARATING |
| | DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR |
| | SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS |
| | (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR |
| | AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E |
| | 90. |
| | |
| | 3C) FLAME SPREAD- FBC-B 2020 603.1. EXCEPTION 2. |
| | INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID |
| | DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED |
| | TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. |
| | |
| | FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS |
| | A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL |
| | MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A |
| | MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723. |
| | |
| | 4) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS |
| | REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT |
| | REVIEW CYCLE. |
| | |
| | PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID |
| | 19 |
| | IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS |
| | 561-718-9724. |
| | WORKING HOURS ARE MON.- WED. 8:00 AM- NOON. PART-TIME/ |
| | RETIRED. |
| | |
| | JAMES A. WITMER BN, PX, SFP, CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES |
| | DEPARTMENT |
| | 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 |
| | TEL: 561-805-6717 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |