| Plan Review Notes For Permit 21051359 |
| Permit Number |
21051359 |
|
| Review Stop |
B |
| Sequence Number |
4 |
|
| Notes |
| Date |
Text |
| 2021-06-25 13:33:47 | JONATHAN BROOKS JR. | | | BUILDING PLANS EXAMINER | | | WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM | | | PHONE (561) 805-6656 | | | EMAIL: [email protected] | | | | | | 1ST REVIEW: FBC 2020 7TH EDITION | | | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) | | | FBC B = FBC BUILDING | | | FBC R = FBC RESIDENTIAL | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC | | | RESULTS: DENIED | | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT | | | CITY HALL, OR EMAIL [email protected] AND REQUEST | | | THAT IT BE CONVERTED TO PROJECTDOX. | | | | | | 1. FBC R 301 FAC9N-3 SUBMITTED FLORIDA DBPR PRODUCT | | | APPROVAL FL16709-R7 SELECTED OPTION FOR SYSTEM NO W-4; | | | EXPOSURE (D); ENCLOSURE (ENCLOSED); ROOF HEIGHT (H<15); | | | ULTIMATE WIND SPEED (180). ZONE 3 IS MARKED ?N/A? WHICH | | | INDICATES SYSTEM IS ?NOT APPLICABLE? TO ZONE1 PRIME | | | DESIGN PRESSURE REQUIREMENTS AND CANNOT BE USED. PLEASE | | | PROVIDE 2020 CODE VERSION PRODUCT APPROVAL/NOA THAT | | | MEETS OR EXCEEDS DESIGN PRESSURE REQUIREMENTS FOR | | | EXPOSURE D AREAS. SIGNED AND SEALED ENGINEERED | | | CALCULATIONS MAY BE REQUIRED. THIRD REQUEST. | | | |
|