Plan Review Notes
Plan Review Notes For Permit 21051312
Permit Number 21051312
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2021-06-25 15:03:50THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) THERE ARE INDICATIONS OF 24' HIGH RACKS.
  
 THERE ARE SLSO INDICATIONS OF AN EXISTING FIRE
 SPRINKLER SYSTEM
  
 THERE ARE NO INDICATIONS THAT THESE RACKS, SHELVING AND
 THE PRODUCTS STORED ARE PROTECTED BY THE FIRE SPRINKLER
 SYSTEM.
  
 PER NFPA 13
  
 3.9.1.17 HIGH-PILED STORAGE. SOLID-PILED, PALLETIZED,
 RACK
 STORAGE, BIN BOX, AND SHELF STORAGE IN EXCESS OF 12 FT
 (3.7 M)
 IN HEIGHT.
  
 16.1.2* SPRINKLER PROTECTION CRITERIA.
 16.1.2.1 SPRINKLER PROTECTION CRITERIA FOR THE STORAGE
 OF MATERIALS
 ON RACKS SHALL BE IN ACCORDANCE WITH SECTION 16.2 FOR
 STORAGE
 UP TO 25 FT (7.6 M) AND SECTION 16.3 FOR STORAGE OVER
 25 FT
  
 PLEASE REVIEW AND PROVIDE SPECIFIC DETAILS THAT THESE
 RACKS AND THE PRODUCTS STORED ON THEM SHALL BE
 PPROTECTED BY THE FIRE SPRINKLER SYSTM IN ACCORDANCE
 WITH THE FIRE CODE.
  
 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  