| Plan Review Notes For Permit 21051312 |
| Permit Number |
21051312 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2021-06-25 15:03:50 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | 1) THERE ARE INDICATIONS OF 24' HIGH RACKS. | | | | | | THERE ARE SLSO INDICATIONS OF AN EXISTING FIRE | | | SPRINKLER SYSTEM | | | | | | THERE ARE NO INDICATIONS THAT THESE RACKS, SHELVING AND | | | THE PRODUCTS STORED ARE PROTECTED BY THE FIRE SPRINKLER | | | SYSTEM. | | | | | | PER NFPA 13 | | | | | | 3.9.1.17 HIGH-PILED STORAGE. SOLID-PILED, PALLETIZED, | | | RACK | | | STORAGE, BIN BOX, AND SHELF STORAGE IN EXCESS OF 12 FT | | | (3.7 M) | | | IN HEIGHT. | | | | | | 16.1.2* SPRINKLER PROTECTION CRITERIA. | | | 16.1.2.1 SPRINKLER PROTECTION CRITERIA FOR THE STORAGE | | | OF MATERIALS | | | ON RACKS SHALL BE IN ACCORDANCE WITH SECTION 16.2 FOR | | | STORAGE | | | UP TO 25 FT (7.6 M) AND SECTION 16.3 FOR STORAGE OVER | | | 25 FT | | | | | | PLEASE REVIEW AND PROVIDE SPECIFIC DETAILS THAT THESE | | | RACKS AND THE PRODUCTS STORED ON THEM SHALL BE | | | PPROTECTED BY THE FIRE SPRINKLER SYSTM IN ACCORDANCE | | | WITH THE FIRE CODE. | | | | | | 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | | ABOVE. | | | | | | 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | | RE-SUBMITTAL OF THE ABOVE. | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|